LiYY Flexible PVC Control and Interconnection Cable – VDE 0812

The LiYY cable delivers dependable data transmission for instrumentation, control engineering, and telecommunication systems. Constructed with flexible plain copper conductors, PVC insulation, and a grey PVC outer sheath, it offers exceptional flexibility and protection. Because it meets VDE 0812 standards and is CE/RoHS compliant, it provides a safe and reliable solution for flexible installations in dry rooms.

Application
LiYY cables provide reliable data transmission in instrumentation and control engineering, particularly where low current consumptions are required. Because they are highly flexible, installers use them in industrial electronics, information and telecommunication systems, and office machines. Furthermore, they are ideal for voice communication in telecommunications systems. Additionally, they are suitable for flexible and permanent installation for unimpeded movement, without tensile load, and without forced movement in dry rooms.

Cable construction
This cable strictly adheres to VDE 0812 standards. It features plain Cu wires, flexible, according to VDE 0295 / IEC 60228 cl.5. The insulation uses a PVC compound type Y12 according to VDE 0207 part 1, with each core twisted to a pair. Pairs are color-coded according to DIN 47100. The cable core wrapping consists of the pairs stranded into layer with plastic foil overlapping. Finally, a PVC compound type YM1 outer sheath (according to VDE 0207 part 5) protects the entire assembly. The sheath color is grey, RAL 7001. Furthermore, this product is both RoHS and CE compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C of 0.26 / 0.34 / 0.50 / 0.75 / 1.0 / 1.5 Ω/km depending on the cross-section. The mutual capacitance at 800 Hz is 150 pF/m. The capacitance unbalance at 800 Hz is 300 pF/m. The insulation resistance is min. 200 MΩ x km. The test voltage is 50 Hz, 1 min, 2000 V. The operating peak voltage is 500 V. The temperature range is fixed -5 °C to +50 °C and flexed -30 °C to +70 °C. The minimum bending radius is 10 x cable diameter.

Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data LiYY…

Number of pairs Cable diameter approx. Cu weight Cable weight approx.
0,2×0,25 mm² mm kg/km kg/km
2 3,7 8 26
4 4,7 15 38
6 5,4 18 50
8 6,3 18,8 54
10 6,9 23,5 16
0,2×0,34 mm²
2 3,9 2,9 15
4 5,1 9,6 32
6 6,1 10,8 39
8 6,7 11,0 42
10 7,4 14,0 47
0,25 mm²
2 4,7 8,5 25
4 5,4 12,2 39
6 7,5 26,2 60
8 7,9 32 70
10 10,2 44,0 118

Construction data LiYY…

Number of pairs Cable diameter approx. Cu weight Cable weight approx.
0,5×0,75 mm² mm kg/km kg/km
2 5,1 14,2 32
3 5,4 18,4 60
4 6,3 28,0 69
5 7,0 38,8 95
7 7,5 56,9 127
0,75×1,0 mm²
2 6,4 19,0 39
4 6,9 35,6 68
6 8,1 58,0 104
10 9,8 76,0 152
12 11,9 88,0 185
1,0×1,5 mm²
3 7,0 25,5 59
4 11,6 43,1 129
5 9,6 54,9 167
6 11,6 83,3 187
7 14,1 139,0 154

(Note: Data for 0.25 mm² and 0.75 mm² variants are transcribed as presented in the source image).

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the LiYY cable?
A:- It is used in instrumentation and control engineering where low current consumptions are required, as well as in industrial electronics, information and telecommunication systems, and office machines.

Q:- What standards does the cable construction follow?
A:- The construction adheres to VDE 0812 standards, and the conductor complies with VDE 0295 / IEC 60228 class 5.

Q:- What type of conductor and insulation does it use?
A:- It uses flexible plain copper wires with a PVC compound type Y12 insulation.

Q:- How are the cores arranged and identified?
A: The cores are twisted to a pair and color-coded according to DIN 47100.

Q:- What is the temperature range for this cable?
A:- The fixed temperature range is -5°C to +50°C, and the flexed temperature range is -30°C to +70°C.

Q:- What is the mutual capacitance of this cable?
A:- The mutual capacitance at 800 Hz is 150 pF/m.

Q:- What is the test voltage for this cable?
A:- The test voltage is 50 Hz, 1 min, 2000 V.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 10 times the cable diameter.

Q:- What is the operating peak voltage?
A:- The operating peak voltage is 500 V.

Q:- Is this cable RoHS and CE compliant?
A:- Yes, the product is both RoHS and CE compliant.