N2XCH 0.6/1 kV Halogen-Free Flame Retardant Cable with Concentric Conductor – VDE 0276-604
The N2XCH 0.6/1 kV cable delivers dependable power distribution for safety-critical environments like power stations, airports, and public buildings. Constructed with copper conductors, XLPE insulation, a copper concentric conductor, and a black halogen-free flame retardant outer sheath, it offers exceptional fire safety with low smoke and corrosion emissions. Because it meets VDE 0276-604 standards and is CE/RoHS compliant, it provides a safe and reliable solution for installations indoors, in air, or in concrete.
Application
N2XCH cables provide reliable power distribution with low halogen fire smoke emission and corrosion at fire conditions. Because of these critical safety features, installers use them in electrical installations for a nominal voltage of 0.6/1 kV. Furthermore, they are essential for important objects like power stations (nuclear, thermal), transformer substations, metro systems, and airports. Additionally, they are ideal for public buildings, hospitals, theaters, cinemas, and commercial centers where the safety of people and material values must be guaranteed. The cables can be laid indoors, in air, or in concrete. However, direct laying underground or in water is not allowed.
Cable construction
This cable strictly adheres to VDE 0276-604 (HD 604 S1) standards. It features copper wires according to VDE 0295 (HD 383) class 1 or 2 (IEC 60228). The insulation uses an XLPE compound 2XI1 (DIX8) according to VDE 0276-604. Core identification follows VDE 0293. A halogen-free compound forms the inner sheath. The concentric conductor consists of plain round copper wires and one or two counter helixes of copper tapes. Finally, a black halogen-free compound flame retardant type LTS 1 sheath protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to VDE 0295 (IEC60228) class 1 or 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of 0.6/1 kV, while the highest system voltage is no more than 1.2 kV. Test voltage is AC – 5 min between cores at 3.5 kV. Installers must respect a minimum bending radius of 6 times the cable diameter. The temperature of laying is no less than 0 °C. The temperature of explosion is -30 to 50 °C. Testing follows VDE 0276-604. Furthermore, it passes the flame retardant test according to VDE 0276-604 / VDE 0472-804 / (IEC 332-3/C and B). The corrosion of combustion gases and conductivity has a pH of min. 4.3 and max. 100 µS/cm. The density of smoke gases follows VDE 0472-816 (IEC 61034-1 and 2).
Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are black or yellow/green. Double core cables feature black and blue, or yellow/green and black. 3-core cables use black, blue, and brown, or yellow/green, blue, and brown. 4-core cables use black, blue, brown, and black, or yellow/green, brown, black, and grey. 5-core cables use black, blue, brown, black, and black, or yellow/green, blue, brown, black, and grey. Multiple core cables use black with number marks on cores or black with number marks on cores and a yellow/green core in the outer cover.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
| Number of wires and nominal cross section | Shape | Concentric conductor cross section | Outer diameter approx. | Cu weight | Cable weight approx. |
|---|---|---|---|---|---|
| N x mm² | mm² | mm | kg/km | kg/km | |
| 1×1,5 | re | 1,5 | 7,9 | 27 | 98 |
| 1×2,5 | re | 2,5 | 8,5 | 41 | 122 |
| 1×4,0 | re | 4,0 | 9,4 | 61 | 163 |
| 1×6,0 | re | 6,0 | 9,8 | 108 | 203 |
| 1×10 | re | 10 | 11,3 | 182 | 286 |
| 1×16 | re | 16 | 12,9 | 272 | 380 |
| 1×25 | rm | 25 | 12,9 | 465 | 606 |
| 1×35 | rm | 35 | 16,4 | 653 | 807 |
| 2×1,5 | re | 1,5 | 13,0 | 65 | 229 |
| 2×2,5 | re | 2,5 | 13,7 | 88 | 270 |
| 2×4,0 | re | 4,0 | 15,0 | 110 | 375 |
| 2×6,0 | re | 6,0 | 15,5 | 177 | 420 |
| 2×10 | re | 10 | 19,1 | 274 | 619 |
| 2×16 | rm | 16 | 21,0 | 483 | 841 |
| 2×25 | rm | 25 | 26,1 | 729 | 1276 |
| 2×35 | rm | 35 | 27,8 | 1080 | 1642 |
| 2×50 | rm | 50 | 31,5 | 1341 | 2193 |
| 3×1,5 | re | 1,5 | 13,5 | 56 | 252 |
| 3×2,5 | re | 2,5 | 14,3 | 90 | 305 |
| 3×4,0 | re | 4,0 | 16,6 | 147 | 425 |
| 3×6,0 | re | 6,0 | 16,7 | 242 | 428 |
| 3×10 | re | 10 | 20,0 | 365 | 724 |
| 3×16 | rm | 16 | 22,1 | 580 | 999 |
| 3×25 | rm | 25 | 26,6 | 938 | 1524 |
| 3×35 | rm | 35 | 29,4 | 1127 | 1813 |
| 3×50 | sm | 50 | 32,7 | 1581 | 2415 |
| 3×70 | sm | 70 | 37,7 | 2333 | 3144 |
| 3×95 | sm | 95 | 38,6 | 2194 | 2800 |
| 3×120 | sm | 120 | 45,2 | 2883 | 4004 |
| 3×150 | sm | 150 | 49,7 | 4038 | 5120 |
| 3×185 | sm | 185 | 54,6 | 5043 | 6392 |
| 4×1,5 | re | 1,5 | 14,3 | 70 | 284 |
| 4×2,5 | re | 2,5 | 15,5 | 113 | 375 |
| 4×4,0 | re | 4,0 | 17,8 | 193 | 494 |
| 4×6,0 | re | 6,0 | 20,0 | 297 | 620 |
| 4×10 | re | 10 | 21,5 | 457 | 860 |
| 4×16 | rm | 16 | 23,5 | 708 | 1124 |
| 4×25 | rm | 25 | 29,0 | 1090 | 1764 |
| 4×35 | rm | 35 | 32,0 | 1365 | 2077 |
| 4×50 | sm | 50 | 38,4 | 1855 | 2910 |
| 4×70 | sm | 70 | 41,9 | 2471 | 3730 |
| 4×95 | sm | 95 | 46,4 | 3531 | 5054 |
| 4×120 | sm | 120 | 48,3 | 4221 | 5898 |
| 4×150 | sm | 150 | 52,3 | 4691 | 7365 |
| 4×185 | sm | 185 | 55,3 | 6214 | 7548 |
| 4×240 | sm | 240 | 62,3 | 8256 | 9374 |
Factory Overview
Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the N2XCH cable?
A:- It is used in electrical installations for a nominal voltage of 0.6/1 kV, particularly in safety-critical environments like power stations, metro systems, airports, hospitals, and public buildings.
Q:- What are the key fire safety features of this cable?
A:- It is halogen-free, flame retardant, and emits low smoke and low-corrosion gases during a fire, passing the VDE 0276-604 / IEC 332-3 tests.
Q:- What standards does the cable construction follow?
A:- The construction adheres to VDE 0276-604 (HD 604 S1) standards, and the conductor complies with VDE 0295 (HD 383) class 1 or 2.
Q:- What type of conductor and insulation does it use?
A:- It uses copper wires with an XLPE compound 2XI1 (DIX8) insulation according to VDE 0276-604.
Q:- What is the function of the concentric conductor?
A:- The concentric conductor, made of plain round copper wires and copper tapes, provides a reliable earth path and enhances mechanical protection.
Q:- Where can this cable be installed?
A:- The cables can be laid indoors, in air, or in concrete. However, direct laying underground or in water is not allowed.
Q:- What is the rated voltage and maximum conductor temperature?
A:- The rated voltage is 0.6/1 kV, and the continuous operating temperature is 90°C.
Q:- What is the short-circuit temperature limit?
A:- It can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.
Q:- What is the test voltage for this cable?
A:- The test voltage is AC – 5 min between cores at 3.5 kV.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 6 times the cable diameter (6x D cable).