2XSY & A2XSY 3.6/6 kV to 20/35 kV XLPE Medium Voltage Cable – IEC 60502-2

The 2XSY and A2XSY cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, and a red PVC outer sheath, they offer excellent thermal and electrical protection for 3.6/6 kV, 8.7/15 kV, and 20/35 kV applications. Because they meet IEC 60502-2 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
2XSY and A2XSY medium voltage cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 3.6/6 kV, 8.7/15 kV, and 20/35 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, and power stations. Because of their robust design, they are suitable for fixed assembly in lines with unlimited difference levels, indoor installations, cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. A layer of plastic tape forms the separating layer. The sheath uses PVC compound type ST2 according to IEC 60502. The color is red. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BDS904 (IEC60228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 3.6/6, 8.7/15, and 20/35 kV, while the highest system voltage Uo/U is not more than 3.6/6, 12/20, and 24/36 kV. Test voltage is AC (+) – 5 min for 3.6/6 kV (10 kV), 8.7/15 kV (30 kV), and 20/35 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XSY, A2XSY 3.6/6; 8.7/15; 20/35 kV

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XSY Mass of Cu approx. 2XSY Mass of cable approx. A2XSY Mass of Al approx. A2XSY Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
3.6/6 kV
1x35m/16 2,5 1,8 16 21,0 493 804 94 176
1x50m/16 2,5 1,8 16 22,1 604 939 127 581
1x70m/16 2,5 1,8 16 23,7 793 1114 183 638
1x95m/16 2,5 1,8 16 25,5 1033 1433 251 746
1x120m/16 2,5 1,8 16 26,9 1255 1686 321 817
1x150m/16 2,5 1,9 16 28,6 1537 1988 384 938
1x185m/25 2,6 2,0 25 30,8 1952 2499 494 1059
1x240m/25 2,6 2,0 25 33,7 2365 2894 639 1193
1x300m/25 2,8 2,1 25 36,5 2763 3039 795 1407
1x400m/35 2,8 2,2 35 39,7 3693 4050 1095 1557
1x500m/35 3,0 2,3 35 43,0 4484 4741 1374 1954
1x630m/35 3,2 2,4 35 43,9 4807 5750 363 2611
8.7/15 kV
1x35m/16 4,5 1,8 16 25,0 493 942 94 719
1x50m/16 4,5 1,8 16 26,1 604 1063 127 782
1x70m/16 4,5 1,8 16 27,8 793 1200 183 830
1x95m/16 4,5 1,9 16 29,7 1033 1619 251 1016
1x120m/16 4,5 1,9 16 31,2 1255 1857 321 1136
1x150m/16 4,5 2,0 16 32,8 1537 2130 384 1280
1x185m/16 4,5 2,1 16 34,7 1942 2590 494 1419
1x240m/16 4,5 2,2 16 37,3 2365 3199 639 1656
1x300m/25 4,5 2,3 25 39,9 2815 3748 795 1900
1x400m/35 4,5 2,5 35 43,7 3730 4826 1095 2363
1x500m/35 4,5 2,5 35 46,3 4489 5016 1374 2473
1x630m/35 4,5 2,5 35 46,6 4807 5750 363 2803
20/35 kV
1x50m/16 8,8 2,1 16 35,3 604 1516 127 1215
1x70m/16 8,8 2,2 16 37,0 793 1572 183 1254
1x95m/16 8,8 2,2 16 38,9 1033 2103 251 1500
1x120m/16 8,8 2,3 16 40,5 1255 2401 321 1643
1x150m/16 8,8 2,3 16 42,0 1537 2522 384 1763
1x185m/25 8,8 2,4 25 43,9 1930 3229 495 2058
1x240m/25 8,8 2,5 25 46,5 2454 3714 649 2359
1x300m/25 8,8 2,6 25 47,0 2860 4416 815 2420
1x400m/35 8,8 2,6 35 52,3 3733 5514 1093 3073
1x500m/35 8,8 2,8 35 55,9 4807 6633 1374 3523

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XSY and A2XSY cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available in three nominal voltage levels: Uo/U 3.6/6 kV, 8.7/15 kV, and 20/35 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 standards, and the conductor complies with IEC 60228 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What type of metal screen is used in the cable?
A:- The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.

Q:- What is the maximum force of strain during laying?
A:- The maximum force of strain is 30NS for Al cores and 50NS for Cu cores, where N is the number of cores and S is the cross-section of conductors in mm.

 

Reviews

There are no reviews yet.

Be the first to review “2XSY & A2XSY 3.6/6 kV to 20/35 kV XLPE Medium Voltage Cable – IEC 60502-2”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS