AGKABEL Middle Voltage Power Cables – 2XSEY/N2XSEY, A2XSEY/NA2XSEY (6/10 kV, 12/20 kV, 18/30 kV) – Three Core

Three-core cables with XLPE insulation designed for power transfer and distribution in urban and district networks. Features Cu or Al stranded compacted conductors, a copper wire screen, and a red PVC sheath. Compliant with IEC 60502-2 / DIN VDE 0276-620 and RoHS. Operating temperature: 90°C continuous. Suitable for transformer substations, power stations, and industrial systems. Available from 35mm² to 300mm².

AGKABEL GRUPPE LIMITED presents the Three-Core Middle Voltage Power Cables (2XSEY, N2XSEY, A2XSEY, NA2XSEY), engineered for reliable power transfer and distribution. These three-core cables feature XLPE insulation and are designed for nominal voltages Uo/U 6/10 kV, 12/20 kV, and 18/30 kV at 50 Hz. They are ideal for urban and district electrical networks, transformer substations, and small to medium industrial plants. Suitable for distribution installations, electric power stations, and industrial systems, they are built for fixed assembly in lines with unlimited difference levels, indoor installations, cable ducts, conduits, shafts, over shelves/grills, directly underground in ditches, and outdoor shelters.

Technical Data

  • Standard: According to IEC 60502 and DIN VDE 0276-620

  • Conductor: Cu and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2

  • Insulation: XLPE compound (with inner and outer semi-conductive layers)

  • Metal screen: Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase

  • Cable assembly: Three insulated and screened phases are twisted with fillings and tape support

  • Inner sheath: PVC compound

  • Sheath: PVC compound type ST2 according to IEC 60502, type DMV 6 according to VDE 0276 (Red)

  • Conductor resistance at 20°C: According to BDS904 (IEC60228) class 2

  • Operating temperature: 90°C continuous operation

  • Overload temperature: 130°C / 100h per year max.

  • Short circuit temperature: 250°C / 5 s max.

  • Nominal voltage Uo/U: 6/10; 12/20; 18/30 kV

  • Highest system voltage Uo/U: 6/10; 12/20 kV (12kV; 24kV)

  • Test voltage: AC (~) – 5 min / DC (=) – 15 min (6/10: 15kV / 48kV; 12/20: 30kV / 96kV)

  • Level of partial discharge: max. 5 pC at 2*Uo

  • Bending radius, min: 15x D cable

  • Temperature of laying: no less than -20°C

  • Temperature of exploitation: -30 to 50°C

  • Application: Designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer’s substations, small and medium industrial plants. Suitable for use in distribution installations, electric power stations and industrial systems.

Technical Specifications Table

Number of conductors and nominal cross section N x mm² Thickness of insulation (mm) Thickness of sheath (mm) Nominal cross-section of screen (mm²) Cable diameter approx. (mm) Mass of Cu approx. (kg/km) Mass of cable approx. (kg/km) Mass of Al approx. (kg/km) Mass of cable approx. (kg/km)
6/10 kV
3×35 rm /16 3,4 2,5 16 46,4 1010 2907 298 2231
3×50 rm /16 3,4 2,5 16 48,8 1363 3408 404 2497
3×70 rm /16 3,4 2,7 16 53,0 1968 4279 584 2965
3×95 rm /16 3,4 2,8 16 57,1 2732 5308 809 3481
3×120 rm /16 3,4 2,9 16 60,3 3440 6195 1023 3899
3×150 rm /25 3,4 3,0 25 64,2 4245 7383 1257 4545
3×185 rm /25 3,4 3,2 25 68,5 5311 8741 1579 5195
3×240 rm /25 3,4 3,4 25 74,3 6981 10817 2071 6153
3×300 rm /25 3,4 3,5 25 79,6 8661 12906 2589 7138
12/20 kV
3×35 rm /16 5,5 2,8 16 56,7 1010 3793 298 3117
3×50 rm /16 5,5 2,9 16 59,3 1363 4345 404 3434
3×70 rm /16 5,5 3,0 16 63,3 1968 5248 584 3934
3×95 rm /16 5,5 3,1 16 67,4 2732 6331 809 4504
3×120 rm /16 5,5 3,2 16 70,6 3440 7275 1023 4979
3×150 rm /25 5,5 3,4 25 74,7 4245 8566 1257 5728
3×185 rm /25 5,5 3,5 25 78,8 5311 9968 1579 6422
3×240 rm /25 5,5 3,7 25 84,5 6981 12155 2071 7491
18/30 kV
3×50 rm /16 8 3,3 16 71,7 1363 5624 404 4713
3×70 rm /16 8 3,4 16 75,8 1968 6610 584 5296
3×95 rm /16 8 3,5 16 79,8 2732 7791 809 5964
3×120 rm /16 8 3,7 16 83,3 3440 8819 1023 6523
3×150 rm /25 8 3,8 25 87,1 4245 10185 1257 7347

(Further dimensions available on request.)

 

Factory Overview



Packaging & Shipping


Fly

 

❓ Frequently Asked Questions (FAQ)

1. What are the primary applications for these cables?
They are designed for transfer and distribution of electrical power in urban and district electrical networks, as well as for the electrical supply of transformer’s substations, small and medium industrial plants, and distribution installations, power stations, and industrial systems.

2. What are the key benefits of XLPE insulation?
XLPE (Cross-linked Polyethylene) insulation offers superior dielectric strength, higher current-carrying capacity, and excellent resistance to thermal deformation, making these cables highly reliable for high-voltage power distribution.

3. What do the different part numbers (2XSEY, NA2XSEY, etc.) mean?

  • 2X: Copper conductor.

  • NA2X: Aluminium conductor.

  • S: Copper wire screen.

  • E: Three-core cable.

  • Y: PVC outer sheath.

4. What is the voltage range of these cables?
They are available in 6/10 kV, 12/20 kV, and 18/30 kV ratings.

5. What is the maximum operating temperature?
The continuous operating temperature is 90°C, with a maximum overload temperature of 130°C (100h/year max) and a short-circuit temperature of 250°C (5s max).

6. What standards do these cables comply with?
They comply with IEC 60502-2 and DIN VDE 0276-620, and are RoHS compliant.

7. What sizes and core configurations are available?
Available in three-core configurations, with conductor sizes ranging from 35mm² to 300mm².

Reviews

There are no reviews yet.

Be the first to review “AGKABEL Middle Voltage Power Cables – 2XSEY/N2XSEY, A2XSEY/NA2XSEY (6/10 kV, 12/20 kV, 18/30 kV) – Three Core”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS