2XS(F)L2Y / N2XS(F)L2Y / A2XS(F)L2Y / NA2XS(F)L2Y 6/10 kV to 18/30 kV Water-Blocking Cable

The 2XS(F)L2Y, N2XS(F)L2Y, A2XS(F)L2Y, and NA2XS(F)L2Y cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, water-blocking tapes, and a radial water-absorbing powder, they offer excellent thermal and moisture protection for 6/10 kV, 12/20 kV, and 18/30 kV applications. Because they meet IEC 60502-2 and DIN VDE 0276-620 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
These medium voltage cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 6/10, 12/20, and 18/30 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for use in distribution installations and cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 and DIN VDE 0276-620 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2 and VDE 0295 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. A layer of semi-conductive water absorbing tapes forms the water resisting element. The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. Additionally, a radial water-absorbing powder provides moisture ingress protection. The sheath uses PE compound type ST7 according to IEC 60502 or type DMP 2 according to VDE 0276. The color is black. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC60228 class 2 and VDE 0295 class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 6/10, 12/20, and 18/30 kV, while the highest system voltage Uo/U is not more than 6/10, 12/20, and 18/30 kV. Test voltage is AC (+) – 5 min for 6/10 kV (15 kV), 12/20 kV (30 kV), and 18/30 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. Water penetration tests are performed according to the region of metallic screen using IEC 60502-2 annex F. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XS(F)L2Y / N2XS(F)L2Y, A2XS(F)L2Y / NA2XS(F)L2Y

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XS(F)L2Y, N2XS(F)L2Y Mass of Cu approx. 2XS(F)L2Y, N2XS(F)L2Y Mass of cable approx. A2XS(F)L2Y, NA2XS(F)L2Y Mass of Al approx. A2XS(F)L2Y, NA2XS(F)L2Y Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
6/10 kV
1x35m/16 3,4 2,5 16 23 28 693 94 176
1x50m/16 3,4 2,5 16 24 29 804 127 176
1x70m/16 3,4 2,5 16 26 31 906 183 745
1x95m/16 3,4 2,5 16 27 32 1013 187 846
1x120m/16 3,4 2,5 16 28 33 1555 187 861
1x150m/16 3,4 2,5 16 30 35 1557 216 861
1x185m/16 3,4 2,5 16 32 37 2091 321 1180
1x240m/16 3,4 2,5 16 34 39 2340 394 1425
1x300m/25 3,4 2,5 25 36 41 3001 474 1514
1x400m/35 3,4 2,5 35 38 45 3722 549 1862
1x500m/35 3,4 2,5 35 43 48 3836 958 2646
1x630m/35 3,4 2,5 35 45 49 4887 1374 2549
12/20 kV
1x35m/16 5,5 2,5 16 27 32 483 1081 94
1x50m/16 5,5 2,5 16 28 33 644 758 176
1x70m/16 5,5 2,5 16 30 35 793 176 861
1x95m/16 5,5 2,5 16 31 36 1073 251 1180
1x120m/16 5,5 2,5 16 33 38 1305 321 1468
1x150m/16 5,5 2,5 16 34 39 1556 384 1487
1x185m/16 5,5 2,5 16 36 41 1842 394 1560
1x240m/16 5,5 2,5 16 39 44 2330 495 1590
1x300m/25 5,5 2,5 25 41 46 2430 648 1695
1x400m/35 5,5 2,5 35 45 49 3826 1043 2317
1x500m/35 5,5 2,5 35 48 52 3966 1374 2640
1x630m/35 5,5 2,5 35 52 57 6073 1374 2537
18/30 kV
1x50m/16 8 2,5 16 33 38 604 127 176
1x70m/16 8 2,5 16 35 41 793 183 1164
1x95m/16 8 2,5 16 38 44 1073 251 1289
1x120m/16 8 2,5 16 38 43 1255 321 1370
1x150m/25 8 2,5 25 39 44 1596 351 1550
1x185m/25 8 2,5 25 41 46 1954 384 1700
1x240m/25 8 2,5 25 43 48 2430 648 1955
1x300m/25 8 2,5 25 46 51 2860 859 2110
1x400m/35 8 2,5 35 48 54 3728 852 2189
1x500m/35 8 2,5 35 52 57 4807 1374 2458
1x630m/35 8 2,5 35 57 57 6482 1374 3343

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XS(F)L2Y cable?
A:- It is designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cable is available in three nominal voltage levels: Uo/U 6/10 kV, 12/20 kV, and 18/30 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 and DIN VDE 0276-620 standards, and the conductor complies with IEC 60228 class 2 and VDE 0295 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What is the function of the water resisting element?
A:- The water resisting element, which is a layer of semi-conductive water absorbing tapes, prevents water ingress along the cable.

Q:- What is the purpose of the radial water-absorbing powder?
A:- The radial water-absorbing powder provides moisture ingress protection by swelling when exposed to water.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.