Al/R 0.6/1 kV Self-Supporting Overhead Cable – NFC 33-209

The Al/R 0.6/1 kV cable delivers dependable power transmission and distribution for low voltage overhead networks. Constructed with aluminum conductors, XLPE insulation, and a self-supporting bundle design, it offers excellent performance for permanent suspension on facades and trees. Because it meets NFC 33-209 standards, it provides a reliable solution for crossing forest areas without the need for clearance.

Application
Al/R power cables provide reliable electrical installations with alternating power networks for overhead lines. They operate efficiently at a nominal voltage Uo/U of 0.6/1 kV or in direct power networks with a maximum voltage according to level 0.9 kV. Because these cables utilize supporting neutral zero conductors, installers use them for building networks in city and urban areas. Furthermore, they permit different types of installations including free-hanging facades, fixed on facades, and interconnections. Additionally, they allow crossing of forest areas without the need of clearance and maintenance openings. Finally, the whole bundle is suspended and carried by the phase insulated conductors, with a supporting zero conductor made of aluminum compound.

Cable construction
This cable strictly adheres to NFC 33-209 standards. It features Al stranded compacted or non-compacted conductors for the phase (main) M and the additional lighting R. The neutral (supporting) N conductor uses Al stranded according to NFC 33-209. The insulation uses XLPE with a minimum 2% carbon black content. The cable lay-up constructions are twisted into a bundle including phase (main) insulated cores (M), neutral supporting insulated core (N), and additional reduced insulated cores for lighting (R). The color is black, and the marking is raised with paint, printed phases with numbers 1,2,3, supporting 0 core (N), EKLABEL NFC 33-209, and additional cores for lighting (R) – EPI and EP2.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a continuous operating temperature of 90 °C. The overload temperature is 130 °C for 100% per year max, and the short circuit temperature is 250 °C for 5 seconds max. It operates at a nominal voltage AC of Uo/U 0.6/1 kV and DC of 0.9 kV, while the highest system voltage AC is not more than 1.2 kV. Test voltage is AC 4 kV for 5 minutes and DC 10 kV for 15 minutes. The minimum bending radius is 18 times the cable diameter. The temperature of laying is no less than -10 °C, with a recommended temperature of 15 °C.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and current carrying capacity.

Construction data Al/R 0.6/1 kV

Number of conductors and nominal cross section Thickness of Insulation M/N/R Diameter of bundle approx. Allowed current in power supply networks Allowed current in distribution networks Al/R Mass of Al cores approx. Al/R Cable weight approx.
N x mm² mm mm A A kg/km kg/km
2×16 1,2 15 – wall and facades 91 126
2×25 1,4 16 – 72-121 / 74 142 165
4×16 1,2 18 – 95-122 / 111 182 260
4×25 1,4 22 – 83-111 / 99 285 395
3×25+54.6+16Mm 1,4/1,6 30 112 – 369 505
3×25+54.6+16Mm+Kx16 1,4/1,6/1,2 30 112/83 – 460 635
3×35+54.6+16Mm 1,6/1,6 33 138 – 455 615
3×35+54.6+16Mm+Kx16 1,6/1,6/1,2 33 138/83 – 546 745
3×50+54.6+16Mm 1,6/1,6 36 168 – 583 725
3×50+54.6+16Mm+Kx16 1,6/1,6/1,2 36 168/83 – 674 860
3×50+54.6+16Mm+Kx25 1,6/1,6/1,4 36 168/111 – 725 925
3×70+54.6+16Mm 1,8/1,6 37 213 – 754 950
3×70+54.6+16Mm+Kx16 1,8/1,6/1,2 40 213/83 – 845 1080
3×70+54.6+16Mm+Kx25 1,8/1,6/1,4 40 213/111 – 896 1150
3×70+70Mm 1,8/1,8 41 213 – 798 964
3×70+70Mm+Kx16 1,8/1,8/1,2 41 213/83 – 888 1115
3×70+70Mm+Kx25 1,8/1,8/1,4 41 213/111 – 940 1185
3×95+54.6+16Mm 1,8/1,6 44 258 – 957 1195
3×95+54.6+16Mm+Kx16 1,8/1,6/1,2 44 258/83 – 1059 1325
3×95+54.6+16Mm+Kx25 1,8/1,6/1,4 44 258/111 – 1110 1355
3×95+70Mm 1,8/1,8 44 258 – 1011 1335
3×95+70Mm+Kx16 1,8/1,8/1,2 44 258/83 – 1102 1615
3×95+70Mm+Kx25 1,8/1,8/1,4 44 258/111 – 1154 1685
3×120+70Mm 1,8/1,8 46 300 – 1225 1445
3×120+70Mm+Kx16 1,8/1,8/1,2 46 300/83 – 1367 1720
3×120+70Mm+Kx25 1,8/1,8/1,4 46 300/111 – 1418 1790
3×120+95Mm 1,8/1,8 47 300 – 1296 1535
3×120+95Mm+Kx16 1,8/1,8/1,2 47 300/83 – 1387 1735
3×120+95Mm+Kx25 1,8/1,8/1,4 47 300/111 – 1439 1805
3×150+70Mm 1,7/1,5 48 343 – 1492 1670
3×150+70Mm+Kx16 1,7/1,5/1,2 48 343/83 – 1573 1785
3×150+70Mm+Kx25 1,7/1,5/1,4 48 344/111 – 1624 1870

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the Al/R cable?
A:- It is used for electrical installations with alternating power networks for overhead lines with nominal voltage Uo/U 0.6/1 kV or in direct power networks with maximum voltage according to level 0.9 kV.

Q:- Where can this cable be installed?
A:- It is suitable for building networks in city and urban areas, on free hanging facades, fixed on facades, and for interconnections.

Q:- What is the advantage of the self-supporting design?
A:- The design allows crossing of forest areas without the need of clearance and maintenance openings, as the whole bundle is suspended and carried by the supporting zero conductor made of aluminum compound.

Q:- What standards does the cable construction follow?
A:- The construction adheres to NFC 33-209 standards.

Q:- What type of conductor and insulation does it use?
A:- It uses Al stranded compacted or non-compacted conductors for phase and lighting, Al stranded for neutral, and XLPE insulation with minimum 2% carbon black content.

Q:- What is the nominal voltage and highest system voltage?
A:- The nominal voltage is Uo/U 0.6/1 kV AC and 0.9 kV DC, and the highest system voltage AC is not more than 1.2 kV.

Q:- What are the operating and short-circuit temperatures?
A:- The continuous operating temperature is 90°C, the overload temperature is 130°C for 100% per year max, and the short circuit temperature is 250°C for 5 seconds max.

Q:- What is the test voltage for this cable?
A:- Test voltage is AC 4 kV for 5 minutes and DC 10 kV for 15 minutes.

Q:- What is the minimum bending radius and laying temperature?
A:- The minimum bending radius is 18 times the cable diameter, and the laying temperature is no less than -10°C with a recommended 15°C.

Q:- How are the cables marked?
A:- The cables are marked with raised paint, printed phases with numbers 1, 2, 3, supporting 0 core (N), EKLABEL NFC 33-209, and additional cores for lighting (R) – EPI and EP2.

Reviews

There are no reviews yet.

Be the first to review “Al/R 0.6/1 kV Self-Supporting Overhead Cable – NFC 33-209”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS