AYBY-O & AYBY-J 0.6/1 kV Armoured Aluminum Power Cable – IEC 60502-1
The AYBY-O and AYBY-J 0.6/1 kV cables deliver dependable power distribution for industrial, domestic, and control applications. Constructed with solid or stranded aluminum conductors, PVC insulation, and steel tape armour, they offer exceptional mechanical protection. Because they meet IEC 60502-1 standards and are CE/RoHS compliant, they provide a safe and reliable solution for underground and outdoor installations requiring extra protection.
Application
AYBY cables provide reliable power distribution in power plants, industrial settings, and switching installations. They also excel in street lighting, domestic power supply connections, and secondary distribution networks. Furthermore, installers use them as control cables for transmitting measurement values and regulating pulses. Because of their robust design, they are preferred for underground applications, interior installations in rooms and cable ducts, and outdoor use. Additionally, they function well in the open air and underground, particularly in areas where mechanical protection is required against accidental contact or damage.
Cable construction
This cable strictly adheres to IEC 60502-1 standards. It features solid or multi-strand aluminum wires (class 1 or 2) that comply with IEC 60228. The insulation uses PVC according to IEC 60502, while core identification follows VDE 0293 (single core-black, multiple core). Additionally, tapes and a filling compound form the inner sheath. The cable includes an armour made of two steel tapes or two galvanized steel tapes. Finally, a black PVC type ST1 sheath (acc. IEC 60502) protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC 60228 class 1 or 2. The maximum conductor temperature reaches +70 °C. During a short circuit, it can withstand +160 °C for no more than 5 seconds. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of AC – 3.5 kV at 50 Hz. Installers must respect a minimum bending radius of 15 times the cable diameter for single-core cables, or 12 times for multi-core cables. Furthermore, it passes the flame test according to IEC 332 part 1.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data AYBY-o/j 0.6/1 kV
| Number of conductors and nominal cross section | Shape | Outer diameter approx. | Al weight approx. | Cable weight approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 2 x 16,0 | re | 17,5 | 38 | 473 |
| 2 x 10,0 | re | 19,1 | 56 | 583 |
| 2 x 16 | rm | 21,0 | 84 | 680 |
| 2 x 25 | rm | 24,8 | 199 | 969 |
| 2 x 35 | rm | 27,3 | 199 | 1129 |
| 2 x 50 | rm | 30,7 | 269 | 1412 |
| 3 x 1,5 | re | 16,3 | 56 | 516 |
| 3 x 2,5 | re | 17,2 | 83 | 618 |
| 3 x 10 | re | 20,0 | 132 | 751 |
| 3 x 16 | rm | 22,1 | 256 | 955 |
| 3 x 25 | rm | 25,1 | 288 | 1270 |
| 3 x 35 | rm | 29,1 | 404 | 1523 |
| 3 x 50 | sm | 32,8 | 584 | 1593 |
| 3 x 70 | sm | 33,0 | 859 | 2036 |
| 3 x 95 | sm | 38,0 | 1023 | 2584 |
| 3 x 120 | sm | 40,0 | 1257 | 3072 |
| 3 x 150 | sm | 44,2 | 1579 | 3819 |
| 3 x 185 | sm | 47,8 | 2071 | 4583 |
| 3 x 240 | sm | 53,3 | 2584 | 5435 |
| 3 x 300 | sm | 58,7 | 3488 | 6688 |
| 3 x 4,0 + 4 | re/re | 19,2 | 110 | 683 |
| 3 x 10 + 6 | rm/re | 21,0 | 162 | 660 |
| 3 x 16 + 10 | rm/rm | 23,2 | 251 | 811 |
| 3 x 25 + 16 | rm/rm | 27,3 | 434 | 1125 |
| 3 x 35 + 16 | rm/rm | 30,1 | 343 | 1334 |
| 3 x 50 + 25 | sm/rm | 33,0 | 476 | 1536 |
| 3 x 70 + 35 | sm/rm | 38,2 | 664 | 2105 |
| 3 x 95 + 50 | sm/rm | 42,4 | 944 | 2629 |
| 3 x 120 + 70 | sm/rm | 45,6 | 1218 | 3083 |
| 3 x 150 + 70 | sm/rm | 50,2 | 1848 | 3829 |
| 3 x 185 + 95 | sm/rm | 54,5 | 2412 | 5364 |
| 3 x 240 + 120 | sm/rm | 60,9 | 3008 | 6889 |
| 3 x 300 + 150 | sm/rm | 66,7 | 111 | 710 |
| 4 x 4,0 | re | 19,5 | 175 | 763 |
| 4 x 10 | re | 23,8 | 299 | 990 |
| 4 x 16 | rm | 27,2 | 512 | 1177 |
| 4 x 25 | rm | 31,9 | 970 | 1706 |
| 4 x 35 | sm | 33,0 | 1192 | 2133 |
| 4 x 50 | sm | 42,4 | 1817 | 2788 |
| 4 x 70 | sm | 45,6 | 2102 | 3262 |
| 4 x 95 | sm | 50,2 | 2762 | 4064 |
| 4 x 120 | sm | 54,5 | 3488 | 4884 |
| 4 x 150 | sm | 60,9 | 4338 | 6184 |
| 4 x 185 | sm | 66,7 | 4522 | 6480 |
| 4 x 240 | sm | 21,0 | 94 | 607 |
| 5 x 1,5 | re | 22,6 | 139 | 807 |
| 5 x 6,0 | rm | 23,2 | 269 | 1070 |
| 5 x 10 | rm | 27,1 | 390 | 1469 |
| 5 x 16 | rm | 31,7 | 673 | 1765 |
| 5 x 25 | rm | 34,9 | 673 | 2479 |
| 5 x 35 | rm | 40,1 |
Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.
Factory Overview
Packaging & Shipping


Frequently asked questions and answer
Q:- What is the primary application of the AYBY cable?
A:- AYBY is used in power plants, industrial and switching installations, for street lighting, domestic power supply, secondary distribution networks, and as control cables.
Q:- What standards does the AYBY cable construction follow?
A:- The construction adheres to IEC 60502-1 standards, and the conductor complies with IEC 60228.
Q:- What type of conductor and insulation does it use?
A:- It uses solid or multi-strand Al wires class 1 or 2 for the conductor and PVC for insulation according to IEC 60502.
Q:- What kind of armour protects this cable?
A:- The cable features an armour made of two steel tapes or two galvanized steel tapes.
Q:- What is the rated voltage and test voltage?
A:- The rated voltage Uo/U is 0.6/1 kV, and it undergoes a test voltage of AC – 3.5 kV at 50 Hz.
Q:- What are the maximum conductor and short circuit temperatures?
A:- The maximum conductor temperature is +70°C, and it can withstand a short circuit temperature of +160°C for no more than 5 seconds.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter for single-core cables and 12 times for multi-core cables.
Q:- What is the color coding for single and multiple-core versions?
A:- Single core cables are black, while multiple core cables follow core identification according to VDE 0293.
Q:- What type of outer sheath protects the cable?
A:- A black PVC type ST1 sheath (according to IEC 60502) protects the entire cable assembly.
Q:- Is this cable flame retardant?
A:- Yes, it passes the flame test according to IEC 332 part 1.