NAYY-O & NAYY-J 0.6/1 kV Aluminum Power Cable – RoHS Compliant
The NAYY-O and NAYY-J 0.6/1 kV cables deliver reliable power distribution for industrial and secondary network applications. Constructed with solid or multi-strand aluminum conductors, PVC insulation, and a black PVC outer sheath, they offer exceptional durability. Because they are RoHS and CE compliant, they provide a safe and cost-effective solution for outdoor, underground, and in-water installations.
Application
NAYY cables provide reliable power distribution in power plants, industrial settings, and switching installations. They also excel in secondary distribution networks. Because of their robust design, installers prefer them for outdoor applications, indoor installations, open air, underground, and even in water. However, you should not use them where mechanical damage is anticipated.
Cable Construction
This cable strictly adheres to VDE 0276 part 603 standards. It features solid or multi-strand aluminum wires (class 1 or 2) that comply with VDE 0295 (IEC 60228). The insulation uses PVC type DIV4 according to VDE0207, while core identification follows VDE 0293. Additionally, a filling compound forms the inner sheath. Finally, a black PVC type DMV5 sheath (acc. VDE 0207) protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to VDE 0295 class 1 or 2 (IEC 60228). The maximum conductor temperature reaches +70 °C. During a short circuit, it can withstand +160 °C for no more than 5 seconds. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of AC – 4 kV at 50 Hz. Installers must respect a minimum bending radius of 15 times the cable diameter for multi-core cables, or 12 times for single-core cables. Furthermore, it passes the flame test according to VDE 0472 part 804 class B (IEC 332 part 1).
Color Coding
Clear color coding ensures safe and accurate wiring. Single core cables are either black or yellow/green. Double core cables feature blue and brown, or yellow-green and black.
Multi-Core Color Configurations
-
3-core: brown, black, grey, or yellow/green, blue, brown
-
4-core: blue, brown, black, grey or yellow/green, brown, black, grey
-
5-core: blue, brown, black, grey, black or yellow/green, blue, brown, black, grey
-
Multiple core: black with number mark on cores, or black with number mark on cores and yellow/green core in the outer cover
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data NAYY o/j 0.6/1 kV
| Number of wires and nominal cross section | Shape | Outer diameter of cable approx. | Al weight | Cable weight approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 1 x 25,0 | re | 12,2 | 70 | 210 |
| 1 x 35,0 | re | 13,1 | 97 | 229 |
| 1 x 50,0 | re | 14,3 | 135 | 283 |
| 1 x 70,0 | rm | 17,1 | 195 | 360 |
| 1 x 95,0 | rm | 18,5 | 261 | 439 |
| 1 x 120,0 | rm | 20,8 | 341 | 589 |
| 1 x 150,0 | rm | 22,6 | 419 | 705 |
| 1 x 185,0 | rm | 24,9 | 526 | 882 |
| 1 x 240,0 | rm | 27,6 | 681 | 1050 |
| 1 x 300,0 | rm | 30,6 | 863 | 1325 |
| 1 x 400,0 | rm | 34,0 | 1109 | 1657 |
| 1 x 500,0 | rm | 38,0 | 1393 | 2172 |
| 2 x 2,5 | re | 12,2 | 14 | 165 |
| 2 x 4,0 | re | 14,4 | 22 | 227 |
| 2 x 6,0 | re | 15,3 | 31 | 255 |
| 2 x 10,0 | re | 16,8 | 52 | 346 |
| 2 x 16,0 | rm | 19,4 | 84 | 486 |
| 2 x 25,0 | rm | 22,4 | 125 | 880 |
| 2 x 35,0 | rm | 25,1 | 199 | 1020 |
| 2 x 50,0 | sm | 27,1 | 269 | 1447 |
| 2 x 70,0 | sm | 33,7 | 390 | 1647 |
| 2 x 95,0 | sm | 37,7 | 538 | 1905 |
| 3 x 1,5 | re | 12,1 | 20 | 168 |
| 3 x 2,5 | re | 12,9 | 27 | 194 |
| 3 x 4,0 | re | 14,9 | 41 | 285 |
| 3 x 6,0 | re | 16,0 | 56 | 314 |
| 3 x 10,0 | sm | 17,6 | 94 | 432 |
| 3 x 16,0 | sm | 27,8 | 404 | 1294 |
| 3 x 25,0 | sm | 27,8 | 404 | 1294 |
| 3 x 35,0 | sm | 30,4 | 504 | 1675 |
| 3 x 50,0 | sm | 33,8 | 859 | 1964 |
| 3 x 70,0 | sm | 38,0 | 1023 | 2391 |
| 3 x 95,0 | sm | 41,0 | 1470 | 2913 |
| 3 x 120,0 | sm | 45,7 | 1579 | 3401 |
| 3 x 150,0 | sm | 51,1 | 2071 | 3603 |
| 3 x 240,0 | sm | 49,5 | 462 | 1310 |
| 3 x 50,0+25 | rm | 30,5 | 462 | 1310 |
| 3 x 70,0+35 | sm | 33,9 | 679 | 1604 |
| 3 x 95,0+50 | sm | 36,0 | 844 | 1971 |
| 3 x 120,0+70 | sm | 38,9 | 1145 | 2396 |
| 3 x 150,0+70 | sm | 46,0 | 1452 | 2789 |
| 3 x 185,0+95 | sm | 52,3 | 1848 | 3470 |
| 3 x 240,0+120 | sm | 55,6 | 2163 | 3902 |
| 3 x 300,0+150 | sm | 64,3 | 3008 | 5321 |
Construction data NAYY o/j 0.6/1 kV
| Number of wires and nominal cross section | Shape | Outer diameter of cable approx. | Al weight | Cable weight approx. |
|---|---|---|---|---|
| N x mm² | mm | kg/km | kg/km | |
| 4 x 25,0 | sm | 25,8 | 281 | 912 |
| 4 x 35,0 | sm | 28,2 | 388 | 1111 |
| 4 x 50,0 | sm | 34,0 | 559 | 1355 |
| 4 x 70,0 | sm | 38,7 | 779 | 1658 |
| 4 x 95,0 | sm | 40,2 | 1079 | 2139 |
| 4 x 120,0 | sm | 48,6 | 1676 | 3115 |
| 4 x 150,0 | sm | 53,7 | 2105 | 4002 |
| 4 x 185,0 | sm | 57,5 | 2782 | 4106 |
| 5 x 1,5 | re | 13,8 | 33 | 191 |
| 5 x 2,5 | re | 15,0 | 32 | 202 |
| 5 x 4,0 | sm | 28,1 | 351 | 1072 |
| 5 x 6,0 | sm | 30,9 | 467 | 1355 |
| 5 x 10,0 | sm | 34,0 | 588 | 1733 |
| 5 x 16,0 | sm | 37,1 | 745 | 1896 |
| 5 x 25,0 | sm | 39,3 | 974 | 2452 |
| 5 x 35,0 | sm | 44,3 | 1349 | 3257 |
| 5 x 50,0 | sm | 49,8 | ||
| 5 x 70,0 | sm | |||
| 5 x 95,0 | sm |
(Note: The data table for the second column ends at 5 x 35,0 in the provided image, with empty rows below. I have left the empty rows blank as per the image.)
Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.
Factory Overview
Packaging & Shipping


Frequently asked questions
What is the Application of NAYY cables?
NAYY is used in power plants industrial and switching installations, in secondary distribution networks and other. These cables are preferably used in outdoor applications, for indoor installations, in the open air, underground and in water where mechanical damage is not anticipated.
What is the Cable construction of NAYY cables?
Construction: According to VDE 0276 part 603
Conductor: solid or multi-strand Al wires class 1 or 2 acc. VDE 0295 (IEC 60228)
Insulation: PVC type DIV4 acc. VDE0207
Core identification: according to VDE 0293
Inner sheath: filling compound
Sheath: PVC type DMV5 acc. VDE 0207
Color: black
What are the Technical data specifications for NAYY cables?
Conductor resistance at 20 °C: According to VDE 0295 class 1 or 2 (IEC 60228)
Max. conductor temperature: +70°C
Max. short circuit temperature: +160°C, not more than 5 sec
Rated voltage Uo/U: 0.6/1 kV
Test voltage: AC – 4 kV 50 Hz
Bending radius -multi core: 15 cable diameter
Bending radius -single core: 12 cable diameter
Flame test: VDE 0472 part 804 class B (IEC 332 part 1)
What is the Color coding for NAYY cables?
Single core – black or yellow/green
Double core – blue and brown or yellow-green and black