AIDC Data Center Power Cable Collection (UL Types)

For UPS, Control Cabinet & High-Density Rack Power


1. Main Power Feed (Utility → Switchgear → UPS → PDU)

Cable TypeUL Std.InsulationVoltageTempApplication
XHHW-2​UL 44XLPE600V (up to 1000V)90°C dry/wetUPS input/output, generator & ATS feeds, tray/conduit
THHN / THWN-2​UL 83PVC + nylon600V90°C dry / 75°C wetGeneral conduit wiring, cost-sensitive runs
TC-ER (XHHW-2 core)​UL 1277XLPE + PVC/CPE jacket600V90°CExposed cable tray, no conduit needed, UPS→PDU feeders
RHH / RHW-2​UL 44XLPE600V90°CAlternative to XHHW-2 in legacy specs

2. AIDC High-Density / Battery / DC Bus

Cable TypeUL Std.InsulationVoltageTempApplication
DCPC (Data Center Power Cable)​UL 2137Flexible XLPE / LSZH optional2000V AC/DC75/90/105/150°CAI rack power, UPS↔BESS battery cabinet, 48V/240V DC bus
Battery Harness (fine-strand)​UL 1973 / UL 9540ALSZH XLPO600–1000V DC125°CUPS string interconnect, BMS sense + power combo
Flexible DC Feeder​UL 1650 (W-type alt.)Rubber/XLPO2000V DC—Portable/industrial DC links (less common in fixed AIDC)

3. Control Cabinet Internal Wiring

Cable TypeUL Std.InsulationVoltageTempApplication
MTW​UL 1063PVC (flexible)600V60/75/90°CPanel power wiring, flexible control circuits
UL 1015 (AWM)​UL 758PVC600V105°CMain control loops, terminal blocks, transformer leads
UL 1007 (AWM)​UL 758PVC300V80°CPLC signals, low-current control, door wiring
TC-ER Shielded​UL 1277XHHW-2 + Cu braid/foil600V90°CUPS↔BMS/CT/PT signal & control in tray

4. Plenum / Raised-Floor Special (NEC 645 / NFPA 262)

  • CMP-rated power/comms cable​ for air-handling spaces (plenum)
  • DP-type (UL 1690)​ for under-floor data hall power distribution (600V, low-flame)

5. Typical Bill-of-Material Template (English)

UPS INPUT FEED
XHHW-2, stranded bare copper, XLPE insulation, 600/1000V, 90°C wet/dry,
sunlight & oil resistant, VW-1, per UL 44 / NEC 310.15
3 x 350 kcmil + 1 x 175 kcmil GND

UPS TO PDU (TRAY)
TC-ER, XHHW-2 conductors, PVC/CPE jacket, 600V, 90°C,
IEEE 1202 / FT4, per UL 1277 / NEC 336
4 x 4/0 AWG + 1 x 2/0 AWG

BATTERY CABINET LINK
DCPC Type, UL 2137, fine-stranded tinned copper, LSZH optional,
2000V AC/DC, 90°C, flexible
2 x 4/0 AWG + shield

CONTROL PANEL
UL 1015 105°C 600V tinned copper, VW-1 (power)
UL 1007 80°C 300V (control/signal)
MTW per UL 1063 for flexible internal harness

6. Quick Selection Rule

  • Building feeder / conduit​ → XHHW-2
  • Open tray, fast install​ → TC-ER (XHHW-2)
  • AI rack / battery flex / 2kV DC​ → DCPC (UL 2137)
  • Cabinet inside​ → UL 1015 + MTW + 1007
  • Plenum/under-floor​ → CMP / DP-type