AGKABEL Halogen-Free Safety Cables NHXCH FE 180 E30 / E90

High-performance circuit integrity cables designed for safety-critical systems. They are halogen-free, flame-retardant, and maintain circuit integrity for 180 minutes (FE 180) under fire conditions, meeting E30 or E90 classification. Suitable for indoor installation in dry and wet zones, in/on/under plaster, and for outdoor installation. Not suitable for direct laying below ground. Compliant with DIN VDE 0266. Nominal voltage: 0.6/1 kV. Available from 2 to 30 cores, 1.5mm² to 240mm².

AGKABEL GRUPPE LIMITED presents the Halogen-Free Safety Cables NHXCH FE 180 E30 or E90, engineered for maximum safety and reliability in emergency situations. These cables are designed to maintain circuit integrity during a fire (FE 180 for 180 minutes), ensuring that critical systems such as fire alarms, emergency lighting, and smoke extraction fans continue to operate. The halogen-free construction prevents the emission of toxic and corrosive gases, and the flame-retardant properties limit fire spread. They are suitable for indoor installation in dry and wet zones, in, on, and under plaster, as well as for outdoor installation (but not for direct laying below ground).

Technical Data

  • Standard: DIN VDE 0266

  • Nominal voltage: 0.6/1 kV

  • Flame-retardant: IEC 332-3

  • Application: For indoor installation in dry and wet zones, in, on and under plaster. Further use for outdoor installation. Not suitable for direct laying below ground.

  • Classification: E30 (maintains circuit integrity for 30 minutes) or E90 (maintains circuit integrity for 90 minutes).

Technical Specifications Table

E30 Series

Part N° N° of cores x cross-sec mm² Outer diameter ca. mm Copper weight kg/km Weight ca. kg/km
11637001 2X1,5 RE/1,5 13,0 52,00 238,00
11637002 2X2,5 RE/2,5 14,0 80,00 275,00
11637003 2X4 RE/4 15,0 123,00 350,00
11637004 2X6 RE/6 16,0 182,00 430,00
11637005 2X10 RE/10 18,0 312,00 590,00
11637006 2X16 RE/16 20,0 489,00 820,00
11637007 3X1,5 RE/1,5 13,0 66,00 250,00
11637008 3X2,5 RE/2,5 14,0 104,00 310,00
11637009 3X4 RE/4 16,0 161,00 400,00
11637010 3X6 RE/6 17,0 240,00 495,00
11637011 3X10 RE/10 19,0 408,00 690,00
11637012 3X16 RE/16 22,0 643,00 970,00
11637013 3X25 RE/16 26,0 904,00 1.350,00
11637014 3X35 RE/16 29,0 1.192,00 1.830,00
11637015 4X1,5 RE/1,5 15,8 81,00 290,00
11637020 4X2,5 RE/2,5 17,0 128,00 355,00
11637021 4X4 RE/4 18,4 200,00 455,00
11637023 4X6 RE/6 19,8 297,00 580,00
11637024 4X10 RE/10 22,1 504,00 820,00
11637025 4X16 RE/16 24,3 796,00 1.150,00
11637035 3X35 RM/35 30,0 1.402,00 2.200,00
11637037 3X70 RM/70 39,0 2.796,00 4.000,00

E90 Series

Part N° N° of cores x cross-sec mm² Outer diameter ca. mm Copper weight kg/km Weight ca. kg/km
11606001 2X1,5 RE/1,5 13,0 52,00 240,00
11606011 2X2,5 RE/2,5 14,0 80,00 290,00
11606021 2X4 RE/4 15,0 123,00 350,00
11606024 2X6 RE/6 16,0 182,00 450,00
11606027 2X10 RE/10 18,0 312,00 640,00
11606030 2X16 RE/16 22,0 489,00 850,00
11606031 3X1,5 RE/1,5 17,0 66,00 260,00
11606012 3X2,5 RE/2,5 18,0 104,00 330,00
11606022 3X4 RE/4 19,0 161,00 420,00
11606025 3X6 RE/6 20,0 240,00 540,00
11606028 3X10 RE/10 22,0 408,00 760,00
11606031 3X16 RE/16 26,0 643,00 1.073,00
11606033 3X25 RM/16 30,0 1.003,00 1.450,00
11606051 3X25 RM/25 28,0 1.003,00 1.650,00
11606035 3X35 RM/16 32,0 1.402,00 1.798,00
11606052 3X35 RM/25 30,0 1.402,00 2.200,00
11606037 3X50 RM/25 36,0 2.000,00 2.400,00
11606053 3X50 RM/50 34,0 2.000,00 2.900,00
11606039 3X70 RM/35 41,0 2.352,00 3.600,00
11606054 3X70 RM/70 39,0 2.796,00 3.800,00
11606041 3X95 RM/50 47,0 3.216,00 4.800,00
11606043 3X120 RM/70 51,0 4.128,00 6.000,00
11606046 4X1,5 RE/1,5 18,0 81,00 310,00
11606023 4X2,5 RE/2,5 19,0 128,00 380,00
11606022 4X4 RE/4 20,0 200,00 500,00
11606026 4X6 RE/6 21,0 297,00 640,00
11606029 4X10 RE/10 24,0 504,00 900,00
11606032 4X16 RE/16 27,0 796,00 1.300,00

(Further dimensions available on request.)

Factory Overview


Packaging & Shipping


Fly

❓ Frequently Asked Questions (FAQ)

1. What are the primary applications for these cables?
They are designed for safety-critical systems such as fire alarms, emergency lighting, and smoke extraction fans. They are suitable for indoor installation in dry and wet zones, in, on, and under plaster, and for outdoor installation (not for direct laying below ground).

2. What is the difference between E30 and E90?

  • E30: The cable maintains circuit integrity for at least 30 minutes in the event of a fire.

  • E90: The cable maintains circuit integrity for at least 90 minutes in the event of a fire.

3. What does “FE 180” mean?
FE 180 indicates that the cable can maintain insulation integrity for 180 minutes under direct flame exposure, which is a key requirement for critical safety circuits.

4. What are the benefits of halogen-free construction?
Halogen-free cables are safer in fire situations as they do not emit toxic or corrosive halogen gases, and they produce minimal smoke, allowing for clearer evacuation routes.

5. What is the voltage rating of these cables?
The nominal voltage is 0.6/1 kV.

6. What standard do these cables comply with?
They comply with DIN VDE 0266.

7. What sizes and core configurations are available?
Available from 2 to 30 cores, with conductor sizes ranging from 1.5mm² to 240mm².