H05VVC4V5-K Oil Resistant PVC Screened Flexible Control Cable
This flexible control cable features a bare copper Class 5 conductor and a robust oil-resistant PVC outer sheath. It is equipped with a tinned copper braided screen for optimal interference protection, making it ideal for machinery in wet and chemical environments.
These flexible control cables are specifically designed for medium mechanical stresses where free movement is required without tensile stress. Because they are intended for use in dry, moist, and wet rooms, they are not suitable for open-air applications. Furthermore, these cables are constructed and tested according to VDE 0271 and are fundamentally oil-resistant. Consequently, they are highly effective in chemical environments, serving as reliable connections for machines in breweries, bottling plants, and car washing facilities.
The cable structure features a bare copper flexible Class 5 conductor according to IEC 228, which is insulated with a PVC compound type TI2. For core identification, 2-core cables utilize black numbered cores, while 3 or more core cables are provided with black numbered cores plus a green-yellow ground wire. Additionally, an inner sheath is applied, followed by a tinned copper braided screen offering approximately 85% coverage to prevent electromagnetic interference. Finally, the cable is protected by an oil-resistant PVC outer sheath (TM5) in a standard grey RAL 7001 color.
Technical Data & Construction Overview:
-
Conductor resistance at 20°C: According to HD 383, IEC 228
-
Core temperature max: 70°C in operation, 150°C in short circuit
-
Rated voltage: Uo/U 300/500 V
-
Test voltage: 2000V 5min (core/core); 2000V 5min (core/screen)
-
Temperature range: Mobile: -5°C to +70°C | Fixed: -40°C to +70°C
-
Radiation resistance: Up to 80 Mrad
-
Oil resistance: VDE 0281-1.3
-
Behaviour in fire: IEC 60332-1, test method B
Construction data H05VVC4V5-K Uo/U – 300/500 V
| Number of wires and nominal cross section mm² | Outer diameter approx. mm | Copper weight kg/km | Cable weight approx. kg/km |
|---|---|---|---|
| 2×0.5 | 8,0 | 30 | 92 |
| 3×0.5 | 8,4 | 38 | 109 |
| 4×0.5 | 9,1 | 46 | 126 |
| 5×0.5 | 10,1 | 58 | 156 |
| 6×0.5 | 10,7 | 58 | 176 |
| 7×0.5 | 10,7 | 60 | 182 |
| 8×0.5 | 12,5 | 72 | 211 |
| 9×0.5 | 12,5 | 80 | 230 |
| 12×0.5 | 13,5 | 105 | 280 |
| 14×0.5 | 14,2 | 114 | 302 |
| 16×0.5 | 15,8 | 137 | 364 |
| 18×0.5 | 16,6 | 110 | 356 |
| 20×0.5 | 18,6 | 238 | 599 |
| 25×0.5 | 20,8 | 298 | 634 |
| 34×0.5 | 22,8 | 387 | 800 |
| 41×0.5 | 23,0 | 349 | 770 |
| 50×0.5 | 25,0 | 470 | 970 |
| 56×0.5 | 26,6 | 503 | 1012 |
| 85×0.5 | 28,4 | 569 | 1198 |
| 2×0.75 | 8,3 | 41 | 102 |
| 3×0.75 | 8,8 | 55 | 130 |
| 4×0.75 | 9,8 | 56 | 150 |
| 5×0.75 | 10,4 | 76 | 176 |
| 6×0.75 | 11,1 | 95 | 206 |
| 7×0.75 | 12,1 | 85 | 235 |
| 8×0.75 | 12,7 | 98 | 268 |
| 9×0.75 | 13,8 | 112 | 285 |
| 12×0.75 | 14,3 | 135 | 327 |
| 14×0.75 | 15,5 | 135 | 352 |
| 16×0.75 | 16,9 | 190 | 488 |
| 24×0.75 | 18,1 | 69 | 148 |
| 30×0.75 | 19,2 | 76 | 176 |
| 41×0.75 | 20,9 | 90 | 207 |
| 56×0.75 | 22,6 | 108 | 235 |
| 85×0.75 | 24,1 | 139 | 273 |
| 7×1.0 | 13,5 | 157 | 314 |
| 8×1.0 | 15,6 | 173 | 345 |
| 12×1.0 | 15,5 | 183 | 380 |
| 12×1.0 | 16,8 | 240 | 500 |
| 14×1.0 | 18,3 | 283 | 560 |
| 19×1.0 | 20,0 | 366 | 723 |
| 24×1.0 | 21,2 | 386 | 850 |
| 30×1.0 | 24,6 | 518 | 1014 |
| 37×1.0 | 26,0 | 702 | 1133 |
| 42×1.0 | 26,8 | 757 | 1281 |
| 56×1.0 | 27,7 | 778 | 1300 |
| 61×1.0 | 27,7 | 790 | 1300 |
| 2×2.5 | 11,4 | 81 | 190 |
| 3×2.5 | 11,7 | 104 | 243 |
| 4×2.5 | 12,3 | 134 | 280 |
| 5×2.5 | 13,9 | 175 | 342 |
| 7×2.5 | 15,9 | 225 | 439 |
| 8×2.5 | 16,7 | 256 | 487 |
| 12×2.5 | 20,6 | 375 | 760 |
| 14×2.5 | 22,5 | 415 | 800 |
| 16×2.5 | 24,3 | 526 | 1032 |
| 25×2.5 | 29,0 | 897 | 1375 |
| 27×2.5 | 29,8 | 971 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer (Q:- A:-)
Q:- What is the maximum operating temperature for this cable?
A:- The maximum core temperature is 70°C during operation.
Q:- Is this cable suitable for open-air applications?
A:- No, it is explicitly designed for dry, moist, and wet rooms but not for open air.
Q:- Does the cable have protection against electromagnetic interference?
A:- Yes, it features a tinned copper braided screen with approximately 85% coverage.
Q:- What is the rated voltage of the H05VVC4V5-K cable?
A:- The rated voltage is Uo/U 300/500 V.
Q:- Can the cable be used in wet environments?
A:- Yes, it is highly suitable for wet rooms and environments like car washing plants.
Q:- What is the minimum temperature for fixed installations?
A:- The fixed installation temperature range extends down to -40°C.
Q:- How are the cores identified?
A:- Cables with 2 cores are black and numbered, while 3 or more cores are black, numbered, with a green-yellow ground.
Q:- Is the outer sheath resistant to oil?
A:- Yes, it is made of an oil-resistant PVC compound type TM5 tested to VDE 0281-1.3.
Q:- What certifications does this product hold?
A:- It is CE marked and fully RoHS compliant.
Q:- What is the fire behavior standard for this cable?
A:- The cable’s fire behavior is tested according to IEC 60332-1, test method B.