N2XSH & NA2XSH 6/10 kV to 12/20 kV Halogen-Free Flame Retardant Cable – VDE 0276-622
The N2XSH and NA2XSH 6/10 kV to 12/20 kV cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, and a black halogen-free flame retardant outer sheath, they offer exceptional fire safety with low smoke and corrosion emissions. Because they meet VDE 0276-622 standards and are RoHS compliant, they provide a safe and reliable solution for indoor installations, cable ducts, and transformer substations.
Application
N2XSH and NA2XSH medium voltage single-core cables provide reliable transfer and distribution of electrical power in networks with a nominal voltage of Uo/U 6/10 and 12/20 kV, and a frequency of 50 Hz. Because they feature halogen-free flame retardant materials, installers use them for the electrical supply of transformer substations and for fixed indoor assembly. Furthermore, they perform reliably in cable ducts, conduits, and on shelves and grilles. However, installers should not lay them directly underground or in water. Additionally, the cables should not be laid in or near nuclear stations.
Cable construction
This cable strictly adheres to DIN VDE 0276-622 standards. It features copper and aluminum stranded compacted wires according to IEC 60228 cl.2 and VDE 0295 cl.2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. The metal screen consists of Cu wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. A layer of plastic tape forms the separating layer. Finally, a black halogen-free compound, flame retardant type HM4 sheath (according to VDE 0276-622) protects the entire assembly. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC60228 class 2 and VDE 0295 class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 6/10 and 12/20 kV, while the highest system voltage Uo/U is not more than 12 kV and 24 kV. Test voltage is AC (+) – 5 min for 6/10 kV (21 kV) and 12/20 kV (42 kV), or DC (-) – 15 min. The minimum bending radius is 15 times the cable diameter. The temperature of laying is no less than -5 °C. The temperature of explosion is -30 to 50 °C. Testing follows VDE 0276-622. Furthermore, it passes the flame retardant test according to VDE 0276-622 (VDE 0472-804 method C) – IEC 332-3/B. The corrosion of combustion gases has a pH of min. 4.3 and conductivity of max. 10 µS/cm. The density of smoke gases follows VDE 0276-622 method (VDE 0472-816).
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data N2XSH, NA2XSH 6/10; 12/20 kV
| Number of conductors and nominal cross section | Thickness of insulation | Thickness of sheath | Nominal cross section of screen | Cable diameter approx. | N2XSH Mass of approx. | N2XSH Mass of approx. | NA2XSH Mass of approx. | NA2XSH Mass of approx. | ||
|---|---|---|---|---|---|---|---|---|---|---|
| N x mm² | mm | mm | mm² | mm | kg/km | kg/km | kg/km | kg/km | ||
| 6/10 kV | ||||||||||
| 1x35m/16 | 3,4 | 2,5 | 16 | 23 | 28 | 493 | 1145 | 94 | 176 | 922 |
| 1x50m/16 | 3,4 | 2,5 | 16 | 24 | 29 | 604 | 1277 | 127 | 176 | 986 |
| 1x70m/16 | 3,4 | 2,5 | 16 | 27 | 32 | 793 | 1487 | 183 | 176 | 1196 |
| 1x95m/16 | 3,4 | 2,5 | 16 | 27 | 32 | 1033 | 1854 | 254 | 176 | 1251 |
| 1x120m/16 | 3,4 | 2,5 | 16 | 29 | 34 | 1255 | 2138 | 321 | 176 | 1371 |
| 1x150m/25 | 3,4 | 2,5 | 25 | 30 | 35 | 1537 | 2539 | 384 | 265 | 1657 |
| 1x185m/25 | 3,4 | 2,5 | 25 | 32 | 37 | 1930 | 2952 | 485 | 265 | 1822 |
| 1x240m/25 | 3,4 | 2,5 | 25 | 34 | 39 | 2454 | 3538 | 649 | 265 | 1996 |
| 1x300m/25 | 3,4 | 2,5 | 25 | 37 | 42 | 2830 | 4466 | 812 | 265 | 2043 |
| 1x400m/35 | 3,4 | 2,5 | 35 | 40 | 45 | 3835 | 5117 | 1043 | 363 | 2668 |
| 1x500m/35 | 3,4 | 2,5 | 35 | 43 | 48 | 4807 | 6209 | 1374 | 363 | 3192 |
| 12/20 kV | ||||||||||
| 1x35m/16 | 5,5 | 2,5 | 16 | 27 | 32 | 493 | 1372 | 94 | 176 | 1148 |
| 1x50m/16 | 5,5 | 2,5 | 16 | 28 | 33 | 604 | 1516 | 127 | 176 | 1196 |
| 1x70m/16 | 5,5 | 2,5 | 16 | 30 | 35 | 793 | 1795 | 183 | 176 | 1382 |
| 1x95m/16 | 5,5 | 2,5 | 16 | 31 | 36 | 1033 | 2100 | 254 | 176 | 1507 |
| 1x120m/16 | 5,5 | 2,5 | 16 | 33 | 38 | 1255 | 2419 | 321 | 176 | 1655 |
| 1x150m/16 | 5,5 | 2,5 | 16 | 34 | 39 | 1537 | 2780 | 384 | 176 | 1868 |
| 1x185m/25 | 5,5 | 2,5 | 25 | 36 | 41 | 1930 | 3299 | 485 | 265 | 2038 |
| 1x240m/25 | 5,5 | 2,5 | 25 | 39 | 44 | 2454 | 4149 | 649 | 265 | 2626 |
| 1x300m/25 | 5,5 | 2,5 | 25 | 41 | 46 | 2830 | 4466 | 812 | 265 | 2609 |
| 1x400m/35 | 5,5 | 2,5 | 35 | 44 | 49 | 3836 | 5478 | 1043 | 363 | 3022 |
| 1x500m/35 | 5,5 | 2,5 | 35 | 47 | 52 | 4807 | 6613 | 1374 | 363 | 3543 |
Factory Overview
Packaging & Shipping
Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the N2XSH and NA2XSH cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district networks and for the electrical supply of transformer substations, suitable for fixed indoor assembly.
Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available in two nominal voltage levels: Uo/U 6/10 kV and 12/20 kV, operating at a frequency of 50 Hz.
Q:- What standards does the cable construction follow?
A:- The construction adheres to DIN VDE 0276-622 standards, and the conductor complies with IEC 60228 class 2 and VDE 0295 class 2.
Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.
Q:- What are the key fire safety features of this cable?
A:- It features a halogen-free flame retardant HM4 sheath, passes the IEC 332-3/B flame test, and emits low-corrosion smoke gases (pH min. 4.3, conductivity max. 10 µS/cm).
Q:- What are the installation restrictions for this cable?
A:- Installers should not lay them directly underground or in water, and they should not be laid in or near nuclear stations.
Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.
Q:- What is the test voltage for this cable?
A:- Test voltage is AC (+) – 5 min for 6/10 kV (21 kV) and 12/20 kV (42 kV), or DC (-) – 15 min.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).
Q:- What are the temperature limits for laying and explosion?
A:- The temperature of laying is no less than -5°C, and the temperature of explosion is -30 to 50°C.