The (N)HXH-FE 180 0.6/1 kV cable delivers dependable power distribution for safety-critical environments like power stations, airports, and tunnels. Constructed with copper conductors, mica tape and XLPE insulation, and an orange halogen-free flame retardant outer sheath, it offers exceptional fire safety with low smoke and corrosion emissions. Because it meets DIN VDE 0266 standards, retains insulation for 180 minutes, and is CE/RoHS compliant, it provides a safe and reliable solution for fixed indoor and outdoor installations.
Application
(N)HXH-FE 180 cables provide reliable power distribution with insulation retention for 180 minutes. Because they feature flame retardant properties with low halogen fire smoke emission and corrosion at fire conditions, installers use them in electrical installations for break-down/signalization and control. Furthermore, they are essential for important objects including power stations, hotels, theaters, airports, tunnels, and public buildings. Additionally, they are ideal for places with a high concentration of people and material values whose safety during a fire must be guaranteed. The cables are designed for fixed laying in dry and wet premises and outdoor, but not directly underground or in water. Laying in cable ducts is allowed provided precautions are taken to guarantee no water collection in the duct.
Cable construction
This cable strictly adheres to VDE 0266 standards. It features copper wires according to VDE 0295 (HD 383) class 1 or 2 (IEC 60228). The insulation uses a double layer insulation consisting of mica tape and cross-linked polymer according to VDE 0297 part 23 H1. Additionally, tapes or an extruded layer form the inner sheath. Finally, an orange plastic compound type HM4 outer sheath (according to VDE 0297 part 24) protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to VDE 0295 (IEC60228) class 1 or 2. The operating temperature reaches 90 °C continuous. During a short circuit, it can withstand 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of 0.6/1 kV and undergoes a test voltage of AC – 4 kV. Installers must respect a minimum bending radius of 15 times the cable diameter. Furthermore, it passes the flame retardancy test according to DIN VDE 0266 part 3 and IEC 331. The retention of insulation according to IEC 331 is 180 minutes. The temperature range is -30 to +70 °C.
Color coding
Clear color coding ensures safe and accurate wiring. Single core cables are black or yellow/green. Double core cables feature blue and brown, or yellow-green and black. Multi-core configurations include specific color sequences for easy identification. For instance, 3-core uses brown, black, and grey, or yellow/green, blue, and brown. 4-core uses blue, brown, black, and grey, or yellow/green, brown, black, and grey. 5-core uses blue, brown, black, grey, and black, or yellow/green, blue, brown, black, and grey. Multiple core uses black with number marks on cores or black with number marks on cores and a yellow/green core in the outer cover.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data (N)HXH FE 180 0.6/1 kV
| Number of conductors and nominal cross section | Cable diameter approx. | Mass of approx. | Mass of cable approx. |
|---|---|---|---|
| N x mm² | mm | kg/km | kg/km |
| 1×1,5re | 8 | 37 | 105 |
| 1×6,0re | 9 | 56 | 130 |
| 1x10re | 10 | 94 | 170 |
| 1x16re | 11 | 149 | 250 |
| 2×1,5re | 12 | 28 | 190 |
| 2×2,5re | 13 | 46 | 220 |
| 2×4,0re | 15 | 75 | 290 |
| 2×6,0re | 15 | 112 | 340 |
| 2x10re | 16 | 188 | 450 |
| 3×1,5re | 15 | 43 | 240 |
| 3×2,5re | 16 | 70 | 290 |
| 3×4,0re | 17 | 112 | 360 |
| 3×6,0re | 18 | 168 | 450 |
| 3x10re | 20 | 282 | 620 |
| 3x16m | 22 | 460 | 830 |
| 3x25m | 28 | 728 | 1280 |
| 4×1,5re | 16 | 57 | 290 |
| 4×2,5re | 17 | 93 | 360 |
| 4×4,0re | 18 | 149 | 440 |
| 4×6,0re | 19 | 223 | 560 |
| 4x10re | 22 | 376 | 760 |
| 4x16m | 26 | 616 | 1050 |
| 4x25m | 30 | 970 | 1600 |
| 4x35m | 33 | 1346 | 1940 |
| 4x50m | 33 | 1817 | 2570 |
| 5×1,5re | 17 | 71 | 330 |
| 5×2,5re | 19 | 116 | 410 |
| 5×4,0re | 20 | 187 | 520 |
| 5×6,0re | 22 | 279 | 660 |
| 5x10re | 24 | 470 | 950 |
| 5x16m | 27 | 767 | 1300 |
| 7×1,5re | 19 | 100 | 380 |
| 12×1,5re | 23 | 171 | 580 |
Factory Overview
Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the (N)HXH-FE 180 cable?
A:- It is used in critical electrical installations for break-down/signalization and control, particularly in power stations, hotels, airports, tunnels, and public buildings.
Q:- What are the key fire safety features of this cable?
A:- It is halogen-free with low smoke and corrosion emissions, flame retardant according to DIN VDE 0266 part 3, and retains insulation for 180 minutes according to IEC 331.
Q:- What standards does the cable construction follow?
A:- The construction adheres to VDE 0266 standards, and the conductor complies with VDE 0295 (HD 383) class 1 or 2 (IEC 60228).
Q:- What type of conductor and insulation does it use?
A:- It uses copper wires with a double layer insulation consisting of mica tape and cross-linked polymer according to VDE 0297 part 23 H1.
Q:- Where can this cable be installed?
A:- It is designed for fixed laying in dry and wet premises and outdoor, but not directly underground or in water. Laying in cable ducts is allowed if precautions are taken to prevent water collection.
Q:- What is the rated voltage and maximum conductor temperature?
A:- The rated voltage is 0.6/1 kV, and the continuous operating temperature is 90°C.
Q:- What is the short-circuit temperature limit?
A:- It can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.
Q:- What is the test voltage for this cable?
A:- The test voltage is AC – 4 kV.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).
Q:- What are the operating temperature limits?
A:- The temperature range for operation is -30 to +70°C.