A2XSY 1x50rm/16 ELFILT High Voltage Cable – Up to 111 kV (IEC 60840)

The A2XSY 1x50rm/16 ELFILT cable delivers dependable power supply for electrostatic filters up to 111 kV. Constructed with an aluminum stranded conductor, XLPE insulation, a copper wire screen, and a red PVC outer sheath, it offers excellent electrical and thermal performance. Because it meets IEC 60502 and IEC 60840 standards and is RoHS compliant, it provides a safe and reliable solution for underground, indoor, and sheltered outdoor installations.

Application
The A2XSY ELFILT high voltage cable provides reliable power supply for electrostatic filters up to 111 kV. Because of its specialized design, installers use it for underground laying, in premises, in cable ducts, and in conduits. Furthermore, it performs reliably in outdoor applications under shelters. Consequently, it delivers consistent performance in demanding high-voltage environments.

Cable construction
This cable strictly adheres to IEC 60502 and similar IEC 60840 standards. It features aluminum stranded compacted wires according to IEC 60228 cl.2 VDE 0295 cl.2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. The metal screen consists of Cu wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. A layer of plastic tape forms the separating layer. The sheath uses a PVC compound type ST2 according to IEC 60502 / DMV 6 according to VDE 0276. The color is red. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. The aluminum current core features a circular multiwire compacted design with a nominal cross-section of 50 mm² and a diameter of 8.2 mm. The insulation thickness is 11 mm, the metal screen cross-section is 16 mm², the sheath thickness is 2.5 mm, and the outer diameter is approximately 40.0 mm. The mass of the core is 131 kg/km, the mass of the cable is 1524 kg/km, and the single bending radius is min. 65 cm. It maintains an electrical resistance of the core at DC and 20°C of 0.641 Ω/km and an electrical resistance of the screen at DC and 20°C of 1.15 Ω/km. The electrical resistance of insulation is 1*10⁵ MΩ.km, and the operating capacity is 0.11 µF/km. The maximum allowed ambient temperature is 90 °C. Test voltage for 15 minutes is 111 kV for AC and 333 kV for DC. The partial discharge at U=50 kV is max. 10 pC. The dielectric loss (tg δ) is max. 30.10⁻⁴. The increase of tg δ (tg δ / tg δ) is U between 15-38 kV max. 10.10⁻⁴ and U between 38-89 kV max. 10.10⁻⁴.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Parameter Value
Aluminium current core
– circular multiwire compacted
– nominal cross-section mm² 50
– diameter mm 8.2
Insulation thickness mm 11.0
Metal screen cross-section mm² 16
Sheath thickness mm 2.5
Outer diameter approx. mm 40.0
Mass of core approx. kg/km 131
Mass of cable kg/km 1524
Bending radius
– single bending cm min. 65
Electrical characteristics
Electrical resistance of core at DC and 20°C Ω/km 0.641
Electrical resistance of screen at DC and 20°C Ω/km 1.15
Electrical resistance of insulation MΩ.km 1*10⁵
Operating capacity µF/km 0.11
Maximum allowed ambient temperature °C 90
Tests
Test voltage /15 min./
AC voltage 111kV
DC voltage 333kV
Partial discharge at U=50 kV – max. 10pC
Dielectric loss / tgδ /, max. 30.10⁻⁴
Increase of tgδ /tgδ/tgδ/
U between 15-38 kV 10.10⁻⁴
U between 38-89 kV 10.10⁻⁴

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the A2XSY ELFILT cable?
A:- It is used for the power supply of electrostatic filters up to 111 kV.

Q:- Where can this cable be installed?
A:- It is suitable for underground laying, in premises, in cable ducts and conduits, and outdoor under shelters.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502 and similar IEC 60840 standards, and the conductor complies with IEC 60228 cl.2 VDE 0295 cl.2.

Q:- What type of conductor and insulation does it use?
A:- It uses Al stranded compacted wires for the conductor and XLPE compound for insulation.

Q:- What are the key electrical characteristics of this cable?
A:- The electrical resistance of the core at 20°C is 0.641 Ω/km, the screen resistance is 1.15 Ω/km, and the operating capacity is 0.11 µF/km.

Q:- What is the maximum allowed ambient temperature?
A:- The maximum allowed ambient temperature for operating the cable is 90°C.

Q:- What is the test voltage for this cable?
A:- The test voltage for 15 minutes is 111 kV for AC and 333 kV for DC.

Q:- What is the maximum partial discharge level?
A:- The partial discharge at U=50 kV is max. 10 pC.

Q:- What is the minimum bending radius for single bending?
A:- The minimum bending radius for single bending is 65 cm.

Q:- What are the dielectric loss specifications?
A:- The maximum dielectric loss (tg δ) is 30.10⁻⁴, and the increase of tg δ is max. 10.10⁻⁴ for both U between 15-38 kV and U between 38-89 kV.

Reviews

There are no reviews yet.

Be the first to review “A2XSY 1x50rm/16 ELFILT High Voltage Cable – Up to 111 kV (IEC 60840)”

Your email address will not be published. Required fields are marked *