Cu/Al XLPE/CTS/PVC/SWA/PVC 3.8/6.6 kV to 19/33 kV Armoured Cable – BS 6622
The Cu/XLPE/CTS/PVC/SWA/PVC and Al/XLPE/CTS/PVC/SWA/PVC cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, galvanized steel wire armour, and a PVC outer sheath, they offer excellent thermal and mechanical protection for 3.8/6.6 kV, 6.35/11 kV, 8.7/15 kV, 12.7/22 kV, and 19/33 kV applications. Because they meet BS 6622 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.
Application
These medium voltage three-core cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 3.8/6.6 kV, 6.35/11 kV, 8.7/15 kV, 12.7/22 kV, and 19/33 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for use in distribution installations and cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.
Cable construction
This cable strictly adheres to BS 6622 standards. It features copper or aluminum stranded compacted conductors according to BS 6360 (IEC 60228) class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. The metal screen can be either -i-option (Cu tapes laid with overlap over each phase) or -ii-option (Cu wires laid concentrically). The cable assembly features three insulated and screened phases with fillers and a tape support. A PVC compound type 9 forms the separating layer. The armour consists of galvanized steel wires, laid concentrically. Finally, a black PVC compound type 9 sheath (according to BS 6755-1/2) protects the entire assembly. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BS 6360 (IEC 60228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 3.8/6.6, 6.35/11, 8.7/15, 12.7/22, and 19/33 kV, while the highest system voltage Uo/U is not more than 7.2, 12, 17.5, 24, and 36 kV. Test voltage is AC (+) – 15 min for 15 kV, 25.5 kV, 35 kV, 51 kV, and 76 kV. The level of partial discharge at 7.5 kV, 12.5 kV, 17.5 kV, 25.5 kV, and 38 kV is max. 10 pC. The minimum bending radius is 12 times the cable diameter, and 10 times adjacent to joints or terminations. The minimum temperature of laying is no less than 0 °C. The temperature of explosion is -30 to 50 °C. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data Cu/XLPE/CTS/PVC/SWA/PVC, Al/XLPE/CTS/PVC/SWA/PVC 3.8/6.6 kV; 6.35/11 kV; 8.7/15 kV; 12.7/22 kV; 19/33 kV
| Number of conductors and nominal cross section | Thickness of insulation | Diameter of Al wires in armour | Thickness of sheath | Cable diameter approx. | Cu/XLPE/CTS/PVC/SWA/PVC Mass of Cu approx. | Cu/XLPE/CTS/PVC/SWA/PVC Mass of cable approx. | Al/XLPE/CTS/PVC/SWA/PVC Mass of Al approx. | Al/XLPE/CTS/PVC/SWA/PVC Mass of cable approx. |
|---|---|---|---|---|---|---|---|---|
| N x mm² | mm | mm | mm | mm | kg/km | kg/km | kg/km | kg/km |
| 3.8/6.6 kV | ||||||||
| 3×35 m | 2,5 | 2,0 | 2,3 | 44,0 | 1010 | 3880 | 295 | 2865 |
| 3×50 m | 2,5 | 2,5 | 2,5 | 47,7 | 1360 | 4340 | 405 | 3090 |
| 3×70 m | 2,5 | 2,5 | 2,6 | 51,4 | 1965 | 5145 | 585 | 3445 |
| 3×95 m | 2,5 | 2,5 | 2,7 | 55,7 | 2730 | 6255 | 805 | 4100 |
| 3×120 m | 2,5 | 2,5 | 2,8 | 59,1 | 3440 | 7965 | 1020 | 5075 |
| 3×150 m | 2,5 | 2,5 | 2,9 | 62,5 | 4245 | 9010 | 1255 | 6020 |
| 6.35/11 kV | ||||||||
| 3×35 m | 3,4 | 2,5 | 2,5 | 48,5 | 1010 | 4175 | 295 | 3165 |
| 3×50 m | 3,4 | 2,5 | 2,6 | 52,4 | 1360 | 5090 | 405 | 4105 |
| 3×70 m | 3,4 | 2,5 | 2,7 | 56,0 | 1965 | 5660 | 585 | 4690 |
| 3×95 m | 3,4 | 2,5 | 2,9 | 60,1 | 2730 | 7425 | 810 | 5720 |
| 3×120 m | 3,4 | 2,5 | 3,0 | 63,7 | 3440 | 8415 | 1020 | 5995 |
| 8.7/15 kV | ||||||||
| 3×35 m | 4,5 | 2,5 | 2,7 | 54,0 | 1010 | 5365 | 295 | 4860 |
| 3×50 m | 4,5 | 2,5 | 2,7 | 57,0 | 1960 | 6580 | 405 | 4925 |
| 3×70 m | 4,5 | 2,5 | 2,8 | 61,0 | 1965 | 6770 | 585 | 5390 |
| 3×95 m | 4,5 | 2,5 | 3,0 | 65,0 | 2730 | 7830 | 810 | 5915 |
| 12.7/22 kV | ||||||||
| 3×50 m | 5,5 | 2,5 | 2,9 | 62,1 | 1860 | 6385 | 405 | 4900 |
| 3×70 m | 5,5 | 2,5 | 3,0 | 65,9 | 1955 | 6980 | 405 | 5195 |
| 3×95 m | 5,5 | 2,5 | 3,2 | 70,5 | 2730 | 8400 | 810 | 6480 |
| 3×120 m | 5,5 | 3,15 | 3,3 | 74,8 | 3440 | 10765 | 1020 | 8345 |
| 3×150 m | 5,5 | 3,15 | 3,4 | 78,8 | 4245 | 11635 | 1255 | 8800 |
| 19/33 kV | ||||||||
| 3×50 m | 8,0 | 3,15 | 3,4 | 75,8 | 1360 | 9600 | 405 | 8035 |
| 3×70 m | 8,0 | 3,15 | 3,5 | 79,6 | 1965 | 9840 | 585 | 8100 |
| 3×95 m | 8,0 | 3,15 | 3,6 | 83,5 | 2730 | 11065 | 810 | 9180 |
Note: Other core configuration and special constructions manufactured upon request.
Factory Overview
Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the Cu/XLPE/CTS/PVC/SWA/PVC cable?
A:- It is designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.
Q:- What are the nominal voltage levels available for this cable?
A:- The cables are available in five nominal voltage levels: Uo/U 3.8/6.6 kV, 6.35/11 kV, 8.7/15 kV, 12.7/22 kV, and 19/33 kV, operating at a frequency of 50 Hz.
Q:- What standards does the cable construction follow?
A:- The construction adheres to BS 6622 standards, and the conductor complies with BS 6360 (IEC 60228) class 2.
Q:- What type of conductor and insulation does it use?
A:- It uses Cu or Al stranded compacted conductors with XLPE insulation.
Q:- What type of metal screen and armour are used?
A:- The metal screen uses Cu tapes laid with overlap or Cu wires laid concentrically, and the armour consists of galvanized steel wires laid concentrically.
Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.
Q:- What is the maximum partial discharge level?
A:- The level of partial discharge is max. 10 pC at the respective test voltages.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 12 times the cable diameter (12x D cable), and 10 times adjacent to joints or terminations.
Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than 0°C, and the temperature of explosion is -30 to 50°C.
Q:- What is the maximum force of strain during laying?
A:- The maximum force of strain is 30NS for Al cores and 50NS for Cu cores, where N is the number of cores and S is the cross-section of conductors in mm.


Reviews
There are no reviews yet.