A2XS(F)2YT & A2XS2YT 12/20 kV Aerial Bundled Cable – IEC 60502-2
The A2XS(F)2YT and A2XS2YT cables deliver dependable power transfer and distribution for medium voltage overhead networks. Constructed with aluminum conductors, XLPE insulation, a supporting St rope, and a black PE outer sheath, they offer excellent mechanical and environmental protection for 12/20 kV applications. Because they meet IEC 60502-2 standards and are RoHS compliant, they provide a safe and reliable solution for crossing forests, boggy terrains, and coastal areas where traditional ground laying is difficult.
Application
A2XS(F)2YT and A2XS2YT medium voltage cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with a nominal voltage of Uo/U 12/20 kV and a frequency of 50 Hz, in urban and district electrical networks. Because these three-phase aerial bundled cables are installed on an supporting element, installers recommend them for specific installations. For instance, they excel in crossing over forests and trees, as well as in boggy terrains where digging a ditch is difficult and expensive. Furthermore, they perform reliably in coastal and highly polluted industrial areas, as well as in ground. Additionally, they prove highly effective and cost-efficient in all cases where laying cables in the ground and construction of overhead lines is hampered.
Cable construction
This cable strictly adheres to IEC 60502-2 standards. It features aluminum stranded compacted conductors according to IEC 60228 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. A layer of semi-conductive water absorbing tapes forms the water resisting element. The metal screen consists of Cu wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. The water resisting element can be either water absorbing insulation tapes or water absorbing powder and a layer of plastic tape. The sheath uses a PE compound type ST7 according to IEC 60502. The color is black. The supporting insulated Strope features a St rope with insulation. The cable lay up is in TRIPLEX, with conductors twisted into a bundle that includes three phase and supporting insulated St rope. Furthermore, this product is RoHS compliant.
Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC60228 class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at a nominal voltage of 12/20 kV, while the highest system voltage Uo/U is not more than 12/20 kV and 24 kV. Test voltage is AC (+) – 5 min for 12/20 kV (42 kV), or DC (-) – 15 min (104 kV). The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2.
Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.
Construction data A2XS2YT, A2XS(F)2YT 12/20 kV
| Number of conductors and nominal cross section | Thickness of insulation | Thickness of sheath | Nominal cross section of screen | Diameter of bundle approx. | Mass of Al approx. | Mass of cable approx. |
|---|---|---|---|---|---|---|
| N x mm² | mm | mm | mm² | mm | kg/km | kg/km |
| 3x(1×50/m/16)+50/50 | 5,5 | 2,5 | 16 | 63 | 570 | 3324 |
| 3x(1×70/m/16)+50/50 | 5,5 | 2,5 | 16 | 68 | 570 | 3621 |
| 3x(1×120/m/16)+50/50 | 5,5 | 2,5 | 16 | 76 | 990 | 4025 |
* Water blocking element is available in cables type A2XS(F)2YT
Note: Other core configuration and special constructions manufactured upon request.
Factory Overview
Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )
Q:- What is the primary application of the A2XS(F)2YT and A2XS2YT cables?
A:- They are designed for the transfer and distribution of electrical power in urban and district electrical networks, specifically recommended for crossing over forests and trees, boggy terrains, and coastal or highly polluted industrial areas.
Q:- What is the nominal voltage level available for this cable?
A:- The cables are available at a nominal voltage level of Uo/U 12/20 kV, operating at a frequency of 50 Hz.
Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 standards, and the conductor complies with IEC 60228 class 2.
Q:- What type of conductor and insulation does it use?
A:- It uses Al stranded compacted conductors with XLPE insulation.
Q:- What is the purpose of the supporting St rope?
A:- The supporting insulated St rope carries the mechanical load of the three-phase aerial bundled cable, allowing for installation in areas where traditional underground laying or overhead line construction is difficult.
Q:- What is the function of the water resisting element?
A:- The water resisting element, which is a layer of semi-conductive water absorbing tapes, prevents water ingress along the cable.
Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.
Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.
Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).
Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.