2XSE(F)2Y / (N)2XSE(F)2Y / A2XSE(F)2Y / (N)A2XSE(F)2Y 6/10 kV to 18/30 kV Water-Blocking Three-Core Cable

The 2XSE(F)2Y, (N)2XSE(F)2Y, A2XSE(F)2Y, and (N)A2XSE(F)2Y cables deliver dependable power transfer and distribution for medium voltage networks. Constructed with copper or aluminum conductors, XLPE insulation, water-blocking tapes, and a PE outer sheath, they offer excellent thermal and moisture protection for 6/10 kV, 12/20 kV, and 18/30 kV applications. Because they meet IEC 60502-2 and DIN VDE 0276-620 standards and are RoHS compliant, they provide a safe and reliable solution for urban networks, substations, and industrial plants.

Application
These medium voltage three-core cables provide reliable transfer and distribution of electrical power in power supply networks. They operate efficiently with nominal voltages of Uo/U 6/10, 12/20, and 18/30 kV, and a frequency of 50 Hz, in urban and district electrical networks. Furthermore, installers use them for the electrical supply of transformer substations, small and medium industrial plants, electric power stations, and industrial systems. Because of their robust design, they are suitable for fixed assembly in lines with unlimited difference levels, indoor installations, cable ducts, conduits, and shafts. Additionally, they perform reliably on shelves and grilles, directly underground in ditch, and outdoor under shelters.

Cable construction
This cable strictly adheres to IEC 60502-2 and DIN VDE 0276-620 standards. It features copper and aluminum stranded compacted conductors according to IEC 60228 class 2 and VDE 0295 class 2. The inner semi-conductive layer, insulation, and outer semi-conductive layer all use XLPE or semi-conductive XLPE compounds. A layer of semi-conductive water absorbing tapes forms the water resisting element. The metal screen consists of copper wires concentrically laid and one contour of Cu tape with a thickness of 0.1 mm. The cable assembly features three insulated and screened cores with a longitudinal water-blocking element twisted in a three-core cable. A filling and inner sheath of PE-LDPE forms the inner sheath, and the sheath uses a PE compound HDPE. The color is black. Furthermore, this product is RoHS compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to BDS904 (IEC60228) class 2. The operating temperature reaches 90 °C continuous. During an overload, it can withstand 130 °C for 100% per year max. In a short circuit, it withstands 250 °C for a maximum of 5 seconds. It operates at nominal voltages of 6/10, 12/20, and 18/30 kV, while the highest system voltage Uo/U is not more than 6/10, 12/20, and 18/30 kV. Test voltage is AC (+) – 5 min for 6/10 kV (15 kV), 12/20 kV (30 kV), and 18/30 kV (48 kV), or DC (-) – 15 min. The level of partial discharge at 2Uo is max. 5 pC. The minimum bending radius is 15 times the cable diameter. The minimum temperature of laying is no less than -20 °C. The temperature of explosion is -30 to 50 °C. Testing follows IEC 60502-2 and DIN VDE 0276-620. The force of strain in laying max is Al cores: 30NS core, Cu cores: 50NS core, where N is the number of cores and S is the cross-section of conductors in mm.

Constructive Data Table
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Construction data 2XSE(F)2Y / (N)2XSE(F)2Y, A2XSE(F)2Y / (N)A2XSE(F)2Y

Number of conductors and nominal cross section Thickness of insulation Thickness of sheath Nominal cross section of screen Cable diameter approx. 2XSE(F)2Y / (N)2XSE(F)2Y Mass of Cu approx. 2XSE(F)2Y / (N)2XSE(F)2Y Mass of cable approx. A2XSE(F)2Y / (N)A2XSE(F)2Y Mass of Al approx. A2XSE(F)2Y / (N)A2XSE(F)2Y Mass of cable approx.
N x mm² mm mm mm² mm kg/km kg/km kg/km kg/km
6/10 kV
3×35 rm/16 3,4 2,5 16 48,5 1010 2715 295 2005
3×50 rm/16 3,4 2,5 16 51,0 1360 3215 405 2210
3×70 rm/16 3,4 2,5 16 56,0 1995 3673 595 2340
3×95 rm/16 3,4 2,9 16 59,0 2730 5125 805 3220
3×120 rm/16 3,4 3,0 16 62,5 3440 6045 1000 3625
3×150 rm/25 3,4 3,1 25 65,5 4245 7110 1255 4445
3×185 rm/25 3,4 3,2 25 70,5 5310 8740 1575 5185
3×240 rm/25 3,4 3,4 25 75,5 6980 10555 2070 6065
12/20 kV
3×35 rm/16 5,5 2,5 16 58,0 1010 3180 295 2445
3×50 rm/16 5,5 2,9 16 60,0 1360 3697 405 2710
3×70 rm/16 5,5 3,0 16 64,5 1985 4550 595 3170
3×95 rm/16 5,5 3,1 16 66,5 2730 5570 805 3650
3×120 rm/16 5,5 3,2 16 71,5 3440 6620 1000 3930
3×150 rm/25 5,5 3,5 25 75,0 4245 7500 1255 4580
3×185 rm/25 5,5 3,5 25 79,0 5310 9150 1575 5100
3×240 rm/25 5,5 3,7 25 85,0 6980 10550 2070 6020
18/30 kV
3×50 rm/16 8,0 3,0 16 72,0 1360 5124 405 3710
3×70 rm/16 8,0 3,4 16 76,0 1965 6100 595 4285
3×95 rm/16 8,0 3,5 16 80,0 2730 6440 805 5160
3×120 rm/16 8,0 3,6 16 83,5 3440 8110 1000 5120
3×150 rm/25 8,0 3,8 25 87,0 4245 9185 1255 7100

Note: Other core configuration and special constructions manufactured upon request.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer ( Q:- A:- )

Q:- What is the primary application of the 2XSE(F)2Y cable?
A:- It is designed for the transfer and distribution of electrical power in urban and district electrical networks and for the electrical supply of transformer substations, small and medium industrial plants, and power stations.

Q:- What are the nominal voltage levels available for this cable?
A:- The cable is available in three nominal voltage levels: Uo/U 6/10 kV, 12/20 kV, and 18/30 kV, operating at a frequency of 50 Hz.

Q:- What standards does the cable construction follow?
A:- The construction adheres to IEC 60502-2 and DIN VDE 0276-620 standards, and the conductor complies with IEC 60228 class 2 and VDE 0295 class 2.

Q:- What type of conductor and insulation does it use?
A:- It uses Cu and Al stranded compacted conductors with XLPE insulation.

Q:- What is the function of the water resisting element?
A:- The water resisting element, which is a layer of semi-conductive water absorbing tapes, prevents water ingress along the cable.

Q:- What is the cable assembly design?
A:- The cable assembly features three insulated and screened cores with a longitudinal water-blocking element twisted in a three-core cable.

Q:- What is the maximum operating and short-circuit temperature?
A:- The maximum operating temperature is 90°C continuous, and it can withstand a short circuit temperature of 250°C for a maximum of 5 seconds.

Q:- What is the maximum partial discharge level?
A:- The level of partial discharge at 2Uo is max. 5 pC.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 15 times the cable diameter (15x D cable).

Q:- What are the temperature limits for laying and explosion?
A:- The minimum temperature of laying is no less than -20°C, and the temperature of explosion is -30 to 50°C.

Reviews

There are no reviews yet.

Be the first to review “2XSE(F)2Y / (N)2XSE(F)2Y / A2XSE(F)2Y / (N)A2XSE(F)2Y 6/10 kV to 18/30 kV Water-Blocking Three-Core Cable”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS