YBY-O & YBY-J 0.6/1 kV Armoured Copper Power Cable – IEC 60502-1

The YBY-O and YBY-J 0.6/1 kV cables deliver dependable power distribution for industrial, domestic, and control applications. Constructed with solid or stranded copper conductors, PVC insulation, and steel tape armour, they offer exceptional mechanical protection. Because they meet IEC 60502-1 standards and are CE/RoHS compliant, they provide a safe and reliable solution for underground and outdoor installations requiring extra protection.

Application
YBY cables provide reliable power distribution in power plants, industrial settings, and switching installations. They also excel in street lighting, domestic power supply connections, and secondary distribution networks. Furthermore, installers use them as control cables for transmitting measurement values and regulating purposes. Because of their robust design, they are preferred for underground applications, interior installations in rooms and cable ducts, and outdoor use. Additionally, they function well in the open air and underground, particularly in areas where mechanical protection is required against accidental contact or damage.

Cable construction
This cable strictly adheres to IEC 60502-1 standards. It features solid or multi-strand copper wires (class 1 or 2) that comply with IEC 60228. The insulation uses PVC according to IEC 60502, while core identification follows VDE 0293 (single core-black, multiple core). Additionally, tapes and a filling compound form the inner sheath. The cable includes an armour made of two steel tapes or two galvanized steel tapes. Finally, a black PVC type ST1 sheath (acc. IEC 60502) protects the entire assembly. Furthermore, this product is both RoHS and CE compliant.

Technical Data
The cable delivers consistent performance under specific conditions. It maintains a conductor resistance at 20 °C according to IEC 60228 class 1 or 2. The maximum conductor temperature reaches +70 °C. During a short circuit, it can withstand +160 °C for no more than 5 seconds. It operates at a rated voltage of 0.6/1 kV and undergoes a test voltage of AC – 3.5 kV at 50 Hz. Installers must respect a minimum bending radius of 18 times the cable diameter for single-core cables, or 12 times for multi-core cables. Furthermore, it passes the flame test according to IEC 332 part 1.

Constructive Data Tables
Please refer to the following comprehensive specifications for precise sizing, weight, and diameter information.

Constructive data YBY-o/j 0.6/1 kV

Number of conductors and nom. cross sec. Shape Outer diameter approx. Cu weight approx. Cable weight approx.
N x mm² mm kg/km kg/km
2 x 4,0 re 16,5 75 566
2 x 6,0 re 17,5 112 592
2 x 10 re 19,1 188 738
2 x 16 rm 21,0 298 878
2 x 25 rm 25,1 485 1277
2 x 35 rm 27,3 673 1447
2 x 50 rm 30,7 908 2016
3 x 1,5 re 17,2 112 524
3 x 2,5 re 18,3 166 654
3 x 4,0 re 19,0 249 748
3 x 6 re 20,0 282 804
3 x 10 rm 22,1 447 1048
3 x 16 rm 23,6 595 1166
3 x 25 rm 28,5 970 1542
3 x 35 rm 30,8 1325 1742
3 x 50 rm 33,8 1363 2408
3 x 70 sm 33,0 1968 2909
3 x 95 sm 36,0 2702 3200
3 x 120 sm 40,0 3420 4000
3 x 150 sm 44,2 4245 5910
3 x 185 sm 47,8 5311 6191
3 x 240 sm 53,3 6981 6184
3 x 300 sm 58,7 8691 11942
3 x 3,0 + 25 sm 29,0 868 1517
3 x 4,0 + 4 re 19,2 205 581
3 x 10 + 6 rm 24,0 384 883
3 x 16 + 10 rm 27,2 563 1170
3 x 25 + 16 rm 31,8 881 1721
3 x 35 + 16 sm 30,1 1103 2108

Constructive data YBY-o/j 0.6/1 kV

Number of conductors and nom. cross sec. Shape Outer diameter approx. Cu weight approx. Cable weight approx.
N x mm² mm kg/km kg/km
3 x 50 + 25 sm/m 33,0 1505 2588
3 x 70 + 35 sm/m 38,2 2304 3659
3 x 95 + 50 sm/m 42,4 3187 4733
3 x 120 + 70 sm/m 47,6 4048 5854
3 x 150 + 70 sm/m 50,2 4901 6854
3 x 185 + 95 sm/m 54,5 6222 8470
3 x 240 + 120 sm/m 60,6 8138 10988
3 x 300 + 150 sm/m 66,7 10076 13112
4 x 4,0 re 18,3 149 607
4 x 6,0 re 19,8 223 728
4 x 10 re 21,4 376 960
4 x 16 rm 23,8 595 1285
4 x 25 rm 29,0 970 1832
4 x 35 rm 31,8 1325 2088
4 x 50 sm 33,0 1817 2815
4 x 70 sm 38,2 2524 3892
4 x 95 sm 42,4 3587 5033
4 x 120 sm 45,6 4547 6313
4 x 150 sm 50,2 5680 7681
4 x 185 sm 54,5 6330 9326
4 x 240 sm 60,9 8308 12012
4 x 300 sm 66,7 11548 14645
5 x 1,5 re 18,8 112 638
5 x 6,0 re 21,0 279 843
5 x 10 re 23,2 470 1120
5 x 16 rm 25,2 744 1548
5 x 25 rm 31,7 1213 2226
5 x 35 rm 34,9 1683 2886
5 x 50 rm 40,0 2371 3994
5 x 70 sm 43,3 3200 4988
7 x 1,5 re 16,9 100 492
10 x 1,5 re 19,9 142 570
12 x 1,5 re 20,4 171 719
14 x 1,5 re 21,2 199 791
16 x 1,5 re 21,9 217 791
19 x 1,5 re 23,0 270 834
20 x 1,5 re 24,0 284 1008
21 x 1,5 re 24,0 284 1008
24 x 1,5 re 26,1 341 1181
27 x 1,5 re 26,6 384 1230
30 x 1,5 re 28,7 426 1336
37 x 1,5 re 29,4 526 1526
7 x 2,5 re 18,0 163 596
10 x 2,5 re 22,6 186 703
12 x 2,5 re 21,5 232 834
16 x 2,5 re 22,6 279 892
19 x 2,5 re 23,9 325 1007
20 x 2,5 re 25,0 441 1183
21 x 2,5 re 25,1 464 1272
24 x 2,5 re 28,6 557 1518
27 x 2,5 re 28,2 627 1602
30 x 2,5 re 30,2 697 1738
37 x 2,5 re 32,3 859 1998
7 x 4,0 re 20,9 261 824
10 x 4,0 re 25,4 373 1212
7 x 6,0 re 22,4 391 1043
10 x 6,0 re 27,9 597 1486

Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

Factory Overview


Packaging & Shipping


Frequently asked questions and answer

Q:- What is the primary application of the YBY cable?
A:- YBY is used in power plants, industrial and switching installations, for street lighting, domestic power supply, secondary distribution networks, and as control cables.

Q:- What standards does the YBY cable construction follow?
A:- The construction adheres to IEC 60502-1 standards, and the conductor complies with IEC 60228.

Q:- What type of conductor and insulation does it use?
A:- It uses solid or multi-strand Cu wires class 1 or 2 for the conductor and PVC for insulation according to IEC 60502.

Q:- What kind of armour protects this cable?
A:- The cable features an armour made of two steel tapes or two galvanized steel tapes.

Q:- What is the rated voltage and test voltage?
A:- The rated voltage Uo/U is 0.6/1 kV, and it undergoes a test voltage of AC – 3.5 kV at 50 Hz.

Q:- What are the maximum conductor and short circuit temperatures?
A:- The maximum conductor temperature is +70°C, and it can withstand a short circuit temperature of +160°C for no more than 5 seconds.

Q:- What is the minimum bending radius for installation?
A:- The minimum bending radius is 18 times the cable diameter for single-core cables and 12 times for multi-core cables.

Q:- What is the color coding for single and multiple-core versions?
A:- Single core cables are black, while multiple core cables follow core identification according to VDE 0293.

Q:- What type of outer sheath protects the cable?
A:- A black PVC type ST1 sheath (according to IEC 60502) protects the entire cable assembly.

Q:- Is this cable flame retardant?
A:- Yes, it passes the flame test according to IEC 332 part 1.

Reviews

There are no reviews yet.

Be the first to review “YBY-O & YBY-J 0.6/1 kV Armoured Copper Power Cable – IEC 60502-1”

Your email address will not be published. Required fields are marked *

RELATED PRODUCTS