AGKABEL Halogen-Free Fire Alarm Cables with Steel Wire Braid – JE-H(St)HQH…Bd (FE 180 E30/E90)
Heavy-duty, flame-resistant telecommunication cables with a red outer sheath and an additional steel wire braid for superior mechanical protection. They maintain circuit integrity for 30 minutes (E30) or 90 minutes (E90) in a fire, and meet the FE 180 standard. Designed for fixed installation with approved cable trays and clamps. Compliant with DIN VDE 0815 and IEC 332-3. Available in pair configurations from 2x2x0.8mm² to 52x2x0.8mm².
AGKABEL GRUPPE LIMITED presents the Halogen-Free Fire Alarm Cables JE-H(St)HQH…Bd, engineered for the most demanding safety-critical environments. The distinct red outer sheath identifies them as fire alarm cables. The key differentiator of this series is the steel wire braid, which provides exceptional mechanical protection against impact, abrasion, and rodent damage—essential in industrial settings or harsh environments. These cables ensure the continued operation of fire alarm systems, emergency lighting, and other critical circuits during a fire. They are available in three performance classifications: E30, E90, and E30/E90 combined. The halogen-free construction ensures minimal smoke and no toxic corrosive gases.
Technical Data
-
Standard: acc. to DIN VDE 0815
-
Flame-retardant: IEC 332-3
-
Application: Flame-resistant telecommunication cable with 30 or 90 min. of circuit integrity in case of fire. For fixed installation with approved cable trays and clamps.
-
Sheath Color: Red (for fire alarm identification)
-
Armour: Steel Wire Braid
-
FE 180: Insulation integrity for 180 minutes (DIN VDE 0472 part 814 / IEC 60331).
-
E30: Functionality for minimum 30 minutes (DIN VDE 4102 part 12).
-
E90: Functionality for minimum 90 minutes (DIN VDE 4102 part 12).
Technical Specifications Table
E30 Series
| Part N° | N° of cores x cross-sec mm² | Outer diameter ca. mm | Copper weight kg/km | Weight ca. kg/km |
|---|---|---|---|---|
| 11614001 | E30 2x2x0,8 | 10,4 | 25,00 | 152,00 |
| 11614002 | E30 4x2x0,8 | 14,7 | 45,00 | 277,00 |
| 11614003 | E30 8x2x0,8 | 21,2 | 85,00 | 544,00 |
| 11614004 | E30 12x2x0,8 | 22,8 | 126,00 | 600,00 |
| 11614005 | E30 16x2x0,8 | 23,6 | 166,00 | 696,00 |
| 11614006 | E30 20x2x0,8 | 26,9 | 206,00 | 868,00 |
| 11614007 | E30 32x2x0,8 | 34,6 | 327,00 | 1.359,00 |
| 11614008 | E30 40x2x0,8 | 40,6 | 407,00 | 1.798,00 |
| 11614009 | E30 52x2x0,8 | 43,7 | 527,00 | 2.040,00 |
E90 Series
| Part N° | N° of cores x cross-sec mm² | Outer diameter ca. mm | Copper weight kg/km | Weight ca. kg/km |
|---|---|---|---|---|
| 11615001 | E90 2x2x0,8 | 10,4 | 25,00 | 152,00 |
| 11615002 | E90 4x2x0,8 | 14,7 | 45,00 | 277,00 |
| 11615003 | E90 8x2x0,8 | 21,2 | 85,00 | 544,00 |
| 11615004 | E90 12x2x0,8 | 22,8 | 126,00 | 600,00 |
| 11615005 | E90 16x2x0,8 | 23,2 | 166,00 | 696,00 |
| 11615006 | E90 20x2x0,8 | 26,9 | 206,00 | 868,00 |
| 11615007 | E90 32x2x0,8 | 34,6 | 327,00 | 1.359,00 |
| 11615008 | E90 40x2x0,8 | 40,6 | 407,00 | 1.798,00 |
| 11615009 | E90 52x2x0,8 | 43,7 | 527,00 | 2.040,00 |
E30/E90 Series
| Part N° | N° of cores x cross-sec mm² | Outer diameter ca. mm | Copper weight kg/km | Weight ca. kg/km |
|---|---|---|---|---|
| 11616001 | E30/E90 2x2x0,8 | 10,4 | 25,00 | 152,00 |
| 11616002 | E30/E90 4x2x0,8 | 14,7 | 45,00 | 277,00 |
| 11616003 | E30/E90 8x2x0,8 | 21,2 | 85,00 | 544,00 |
| 11616004 | E30/E90 12x2x0,8 | 22,8 | 126,00 | 600,00 |
| 11616005 | E30/E90 16x2x0,8 | 23,2 | 166,00 | 696,00 |
| 11616006 | E30/E90 20x2x0,8 | 26,9 | 206,00 | 868,00 |
| 11616007 | E30/E90 32x2x0,8 | 34,6 | 327,00 | 1.359,00 |
| 11616008 | E30/E90 40x2x0,8 | 40,6 | 407,00 | 1.798,00 |
| 11616009 | E30/E90 52x2x0,8 | 43,7 | 527,00 | 2.040,00 |
Factory Overview
Packaging & Shipping


❓ Frequently Asked Questions (FAQ)
1. What are the primary applications for these cables?
They are essential for fire alarm systems and other safety-critical circuits (like emergency lighting and smoke extraction) that must remain operational during a fire. The steel wire braid makes them particularly suited for harsh or industrial environments where mechanical damage is a risk.
2. What is the benefit of the steel wire braid?
The steel wire braid provides exceptional mechanical protection against impact, abrasion, and rodent damage, ensuring the cable’s integrity is maintained even in tough physical conditions.
3. Why is the outer sheath colored red?
The red outer sheath is the industry standard for fire alarm cables, ensuring quick and easy identification by installers and emergency personnel.
4. What is the difference between E30 and E90?
-
E30: Guarantees circuit integrity (functionality) for a minimum of 30 minutes during a fire.
-
E90: Guarantees circuit integrity for a minimum of 90 minutes, providing a longer window for evacuation and emergency operations.
5. What does “FE 180” mean?
FE 180 indicates that the cable maintains insulation integrity for 180 minutes under direct flame exposure (tested according to IEC 60331), ensuring it does not short-circuit even in extreme conditions.
6. What is the installation requirement for these cables?
They must be installed with approved cable trays and clamps to ensure they maintain circuit integrity during a fire.
7. What sizes and pair configurations are available?
Available in pair configurations from 2x2x0.8mm² to 52x2x0.8mm² across the E30, E90, and E30/E90 series.